30 Process Image WAGO-I/O-SYSTEM 750
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0
Table 18: Status Byte S0
Status Byte S0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg_Com
Err_L1
Channel_ID
ProcDat_ID
ProcDat_
ID
Process data index for the physical variable which was read out using input data
word 1.
Channel_
ID
Simple
process
image
Always 0
(With the simple process image the channel index has no significance.)
Flexible
process
image
Channel index for the channel from which a measured value was read
out using input data word 1
Err_L1
0:
The voltage between L1 and N is greater than the set undervoltage
threshold.
1:
The voltage between L1 and N is less than the set undervoltage
threshold. The LED ā€žBā€œ lights up.
Reg_Com
0:
Process data communication
1:
Register communication