EasyManua.ls Logo

Watts AERCO Benchmark BMK5000 - Page 126

Watts AERCO Benchmark BMK5000
213 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 7 BOILER SEQUENCING TECHNOLOGY
OMM-0145_D GF-218 11/2/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 126 of 213
OPTION 7 Instructions: Remote Setpoint, Modbus Header Temp Sensor & 4-20ma Setpoint
Drive
OPTION 7 Step 3: CONNECT BOILERS IN DAISY CHAIN
1. Connect the boilers in a daisy chain, as shown below.
OPTION 7 Step 4: OPTION 7 CONFIGURATION
Using the Modbus Transmitter gives the plant the ability to use the Backup manager
feature. This allows any of the client units to become a Backup manager if the manager
unit is not communicating.
On All Boilers:
1. Go to: Main Menu Advanced Setup BST Cascade Cascade Configuration:
Set the Unit Mode parameter to BST Client.
2. Go to: Main Menu Advanced Setup BST Cascade Cascade Communication:
Set the Unit Address parameter to the communication address of the unit.
Continued on next page
SD-A-1012 rev C

Table of Contents

Other manuals for Watts AERCO Benchmark BMK5000

Related product manuals