Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OMM-0145_D • GF-218 • 11/2/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 127 of 213
OPTION 7 Instructions: Remote Setpoint, Modbus Header Temp Sensor & 4-20ma Setpoint
Drive
On the BST Manager only:
1. Go to Main Menu → Advanced Setup → BST Cascade, set the Parameters to the Values
in each menu in the table below.
Enabled (This is available on the Manager
unit only)
Enter the designated backup unit address
Application
Configuration
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.
* Be sure that the SW1-4 DIP switch on Controller’s Interface Board is set appropriately (On = Current, Off
= Voltage.)