EasyManuals Logo

Watts AERCO Benchmark BMK5000 User Manual

Watts AERCO Benchmark BMK5000
213 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 4 INITIAL START-UP
OMM-0145_D GF-218 11/2/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 61 of 213
NATURAL GAS Manual Combustion Calibration Instructions
TABLE 4-3c: NATURAL GAS Final Valve Positions: BMK1500/2000 Duel Fuel
Valve %
BMK1500 DF
BMK2000 DF
NOx
CO
O
2
%
70%
6.0% ± 0.2%
6.5% ± 0.2%
≤20 ppm
<100 ppm
50%
6.3% ± 0.2%
6.5% ± 0.2%
≤20 ppm
<100 ppm
40%
7.0% ± 0.2%
6.5% ± 0.2%
≤20 ppm
<50 ppm
30%
7.0% ± 0.2%
6.5% ± 0.2%
≤20 ppm
<50 ppm
16%
8.0% ± 0.2%
5.5% ± 0.2%
≤20 ppm
<50 ppm
TABLE 4-3d: NATURAL GAS Final Valve Positions: BMK2500/3000
BMK2500 Single and Duel Fuel
Single Fuel
Dual Fuel
NOx
CO
Valve %
O
2
%
Valve %
O
2
%
70%
5.9% ± 0.2%
70%
5.9% ± 0.2%
≤20 ppm
<100 ppm
50%
6.0% ± 0.2%
45%
6.2% ± 0.2%
≤20 ppm
<100 ppm
40%
6.3% ± 0.2%
30%
6.0% ± 0.2%
≤20 ppm
<50 ppm
30%
6.3% ± 0.2%
20%
5.8% ± 0.2%
≤20 ppm
<50 ppm
16%
6.0% ± 0.2%
16%
6.0% ± 0.2%
≤20 ppm
<50 ppm
BMK3000 Single and Duel Fuel
70%
5.1% ± 0.2%
85%
5.4% ± 0.2%
≤20 ppm
<100 ppm
50%
6.1% ± 0.2%
65%
5.5% ± 0.2%
≤20 ppm
<100 ppm
40%
5.0% ± 0.2%
45%
5.7% ± 0.2%
≤20 ppm
<50 ppm
30%
6.4% ± 0.2%
30%
5.6% ± 0.2%
≤20 ppm
<50 ppm
14%
6.4% ± 0.2%
14%
6.2% ± 0.2%
≤20 ppm
<50 ppm
TABLE 4-3e: NATURAL GAS Final Valve Positions: BMK4000
Valve Position
Standard NOx
Ultra-Low NOx
CO
Single Fuel
O
2
%
NOx
O
2
%
NOx
70%
5.5% ± 0.2%
≤20 ppm
6.0% ± 0.2%
≤9 ppm
<100 ppm
50%
5.5% ± 0.2%
≤20 ppm
6.0% ± 0.2%
≤9 ppm
<100 ppm
40%
5.5% ± 0.2%
≤20 ppm
6.0% ± 0.2%
≤9 ppm
<50 ppm
30%
5.5% ± 0.2%
≤20 ppm
6.0% ± 0.2%
≤9 ppm
<50 ppm
23%
6.0% ± 0.2%
≤20 ppm
6.5% ± 0.2%
≤9 ppm
<50 ppm
TABLE 4-3f: NATURAL GAS Final Valve Positions: 5000N
Valve Position
Standard NO
x
Ultra-Low NO
x
CO
O
2
%
NO
x
O
2
%
NO
x
70%
5.5% ± 0.2%
≤20 ppm
7.5% ± 0.2%
≤9 ppm
<100 ppm
50%
5.5% ± 0.2%
≤20 ppm
7.5% ± 0.2%
≤9 ppm
<100 ppm
40%
5.5% ± 0.2%
≤20 ppm
7.5% ± 0.2%
≤9 ppm
<50 ppm
30%
5.5% ± 0.2%
≤20 ppm
7.5% ± 0.2%
≤9 ppm
<50 ppm
18%
6.0% ± 0.2%
≤20 ppm
7.5% ± 0.2%
≤9 ppm
<50 ppm

Table of Contents

Other manuals for Watts AERCO Benchmark BMK5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts AERCO Benchmark BMK5000 and is the answer not in the manual?

Watts AERCO Benchmark BMK5000 Specifications

General IconGeneral
BrandWatts
ModelAERCO Benchmark BMK5000
CategoryBoiler
LanguageEnglish

Related product manuals