36
WIKA operating instructions process transmitter, model UPT-2x
14111166.02 04/2015 EN/DE
EN
8. Conguration via display and operating unit
8.2.4 Setting the density unit and density value
1. Open the operating menu with [↵].
Select “Basic setting” and conrm with [↵].
2. Select Application” and conrm with [↵].
3. Select “Level” and conrm with [↵].
4. Select “Density” and conrm with [↵].
5. Select “Density unit” and conrm with [↵].
6. Select unit and conrm with [↵].
» Density unit is set.
7. Select “Density value” and conrm with [↵].
8. Set digit using [▲] [▼] and conrm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
»Density value is set.
8.2.5 To set the temperature unit
Temperature unit °C and °F selectable.
1. Open the operating menu with [↵].
Select “Basic setting” and conrm with [↵].
2. Select Application” and conrm with [↵].
3. Select “Sensor temp. and conrm with [↵].
4. Select temperature unit and conrm with [↵].
» Temperature unit is set.