WIKA operating instructions process transmitter, model UPT-2x
14111166.02 04/2015 EN/DE
EN
8. Conguration via display and operating unit
4. Select “Mounting corr.” and conrm with [↵].
5. Select “change” and conrm with [↵].
6. Change digit using [▲] [▼] and conrm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
» Entered value will be used as the new zero point.
8.6 Setting the damping
The damping prevents the uctuation of the output signal when there are short-term
uctuations in the measured value. Safety shut-downs due to turbulent processes are
thus prevented.
Pressure spikes will still be registered, e.g. as P
max
in the menu point
“Diagnostic”.
Setting range 0 ... 99.9 s
1. Open the operating menu with [↵].
Select “Basic setting” and conrm with [↵].
2. Select “Damping value” and conrm with [↵].
3. Change digit using [▲] [▼] and conrm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
» Damping is set.