EasyManua.ls Logo

Wilo Control SC-Booster - Page 119

Wilo Control SC-Booster
1795 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English
48 WILO SE 09/2018
NOTICE:
The maximum number of connections per hour
specified in the table for each power is determined
by the pump motor and must not be exceeded
(adjust the parameterisation of the controller
accordingly; see follow-up times, for example).
2.2 0.167 30
3.0 0.204 6
3.0 0.148 12
3.0 0.122 18
3.0 0.107 24
4.0 0.130 6
4.0 0.094 12
4.0 0.077 18
5.5 0.115 6
5.5 0.083 12
5.5 0.069 18
7.5 0.059 6
7.5 0.042 12
9.0 11.0 0.037 6
9.0 11.0 0.027 12
15.0 0.024 6
15.0 0.017 12
3~400 V
5.5 0.252 18
2-pole
5.5 0.220 24
S-D starting
5.5 0.198 30
7.5 0.217 6
7.5 0.157 12
7.5 0.130 18
7.5 0.113 24
9.0 11.0 0.136 6
9.0 11.0 0.098 12
9.0 11.0 0.081 18
9.0 11.0 0.071 24
15.0 0.087 6
15.0 0.063 12
15.0 0.052 18
15.0 0.045 24
18.5 0.059 6
18.5 0.043 12
18.5 0.035 18
22.0 0.046 6
22.0 0.033 12
22.0 0.027 18
Power [kW]
(Column 1)
System impedance [Ω]
(Column 2)
Connections per hour
(Column 3)

Table of Contents