52 WILO SE 09/2018
Zadržavamo pravo na tehničke izmjene!
40083 -
40084
(82-83)
Ukupni uklopno-isklopni
ciklusi pumpe 2
UINT32 R 31.000
40085 -
40086
(84-85)
Ukupni uklopno-isklopni
ciklusi pumpe 3
UINT32 R 31.000
40087 -
40088
(86-87)
Ukupni uklopno-isklopni
ciklusi pumpe 4
UINT32 R 31.000
40097 -
40098
(96-97)
Ukupni pogonski sati
pumpe 1
UINT32 1 h R 31.000
40099 -
40100
(98-99)
Ukupni pogonski sati
pumpe 2
UINT32 1 h R 31.000
40101 -
40102
(100-101)
Ukupni pogonski sati
pumpe 3
UINT32 1 h R 31.000
40103 -
40104
(102-103)
Ukupni pogonski sati
pumpe 4
UINT32 1 h R 31.000
40139 -
40140
(138-139)
Status pogreške BITMAP32 0: Sensor error
1: P man
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6 Alarm
11: -
12: -
13: Frost
14: Battery Low
15: High water
16: Priority off
17: Redundancy
18: Plausibility
19: Slave communication
20: Net supply
21: Leakage
R 31.000
40141
(140)
Acknowledge BOOL W 31.000
40142
(141)
Kazalo povijesti alarma UINT16 RW 31.000
40143
(142)
Povijest alarma
Broj pogreške
UINT16 0.1 R 31.000
40147
(146)
Kazalo histograma
alarma
UINT16 RW 31.000
40148
(147)
Histogram alarma
Broj pogreške
UINT16 0.1 R 31.000
40149
(148)
Histogram alarma
Učestalost pogreške
UINT16 R 31.000
Holding
registar
Ime Vrsta
podatka
Skaliranje
i jedinica
Elementi Pristup Dodano