52 WILO SE 09/2018
Zadržavamo pravo na tehničke izmene!
40083 -
40084
(82-83)
Ukupan broj radnih
ciklusa pumpe 2
UINT32 R 31,000
40085 -
40086
(84-85)
Ukupan broj radnih
ciklusa pumpe 3
UINT32 R 31,000
40087 -
40088
(86-87)
Ukupan broj radnih
ciklusa pumpe 4
UINT32 R 31,000
40097 -
40098
(96-97)
Ukupan broj radnih sati
pumpe 1
UINT32 1 h R 31,000
40099 -
40100
(98-99)
Ukupan broj radnih sati
pumpe 2
UINT32 1 h R 31,000
40101 -
40102
(100-101)
Ukupan broj radnih sati
pumpe 3
UINT32 1 h R 31,000
40103 -
40104
(102-103)
Ukupan broj radnih sati
pumpe 4
UINT32 1 h R 31,000
40139 -
40140
(138-139)
Status greške BITMAP32 0: Sensor error
1: P man
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6 Alarm
11: -
12: -
13: Frost
14: Battery Low
15: High water
16: Priority off
17: Redundancy
18: Plausibility
19: Slave communication
20: Net supply
21: Leakage
R 31,000
40141
(140)
Acknowledge BOOL W 31,000
40142
(141)
Indeks istorije alarma UINT16 RW 31,000
40143
(142)
Istorija alarma
Broj greške
UINT16 0,1 R 31,000
40147
(146)
Indeks histograma
alarma
UINT16 RW 31,000
40148
(147)
Histogram alarma
Broj greške
UINT16 0,1 R 31,000
40149
(148)
Histogram alarma
Učestalost greške
UINT16 R 31,000
Holding
registar
Naziv Tip
podataka
Skaliranje
i jedinica
Elementi Pristupa Dodato