Français
Notice de montage et de mise en service Wilo-Control SC-Booster (SC, SC-FC, SCe) 51
40035
(34)
Statut de la pompe 3 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31.000
40036
(35)
Statut de la pompe 4 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31.000
40041
(40)
Mode de pompe 1 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40042
(41)
Mode de pompe 2 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40043
(42)
Mode de pompe 3 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40044
(43)
Mode de pompe 4 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40062
(61)
État général BITMAP 0: SBM
1: SSM
R 31.000
40068
(67)
Valeur de consigne 1 UINT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
RW 31.000
40069
(68)
Valeur de consigne 2 UINT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
RW 31.000
40074
(73)
Application ENUM 0. Booster
1. HVAC
2. WP
3. Lift
4. FFS-Diesel
5. FFS-Electro
6. FLA
7. Clean
8. Rain
R 31.101
40075
(74)
Valeur de consigne
externe
INT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
R 31.000
40076
(75)
Activer la valeur de
consigne externe
BOOL RW 31.000
40077 –
40078
(76-77)
Nombre de procédures
d'enclenchement de
l'installation
UINT32 R 31.000
40079 –
40080
(78-79)
Données du coffret de
commande heures de
service
UINT32 1h R 31.000
40081 –
40082
(80-81)
Total des cycles de
manœuvre de la pompe 1
UINT32 R 31.000
Registre
d'exploitation
Nom Type de
donnée
Échelle
et unité
Éléments Accès Ajouté