Inbouw- en bedieningsvoorschriften Wilo-Control SC-Booster (SC, SC-FC, SCe) 51
40035
(34)
Pompstatus 3 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31.000
40036
(35)
Pompstatus 4 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31.000
40041
(40)
Pompmodus 1 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40042
(41)
Pompmodus 2 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40043
(42)
Pompmodus 3 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40044
(43)
Pompmodus 4 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40062
(61)
Algemene status BITMAP 0: SBM
1: SSM
R 31.000
40068
(67)
Gewenste waarde 1 UINT16 0,1 bar
0,1 m
0,1 K
0,1 °C
0,1 psi
RW 31.000
40069
(68)
Gewenste waarde 2 UINT16 0,1 bar
0,1 m
0,1 K
0,1 °C
0,1 psi
RW 31.000
40074
(73)
Toepassing ENUM 0. Booster
1. HVAC
2. WP
3. Lift
4. FFS-Diesel
5. FFS-Electro
6. FLA
7. Clean
8. Rain
R 31.101
40075
(74)
Externe gewenste
waarde
INT16 0,1 bar
0,1 m
0,1 K
0,1 °C
0,1 psi
R 31.000
40076
(75)
Externe gewenste
waarde activeren
BOOL RW 31.000
40077 -
40078
(76-77)
Aantal inschakelingen
van de installatie
UINT32 R 31.000
40079 -
40080
(78-79)
Bedrijfsuren-gegevens
schakeltoestel
UINT32 1 h R 31.000
40081 -
40082
(80-81)
Totale schakelcycli
pomp 1
UINT32 R 31.000
Houd
-
register
Naam Gegevens
-
type
Schalering
& eenheid
Elementen Toegang Toege-
voegd