Instrucciones de instalación y funcionamiento Wilo-Control SC-Booster (SC, SC-FC, SCe) 51
40035
(34)
Estado de bomba 3 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31.000
40036
(35)
Estado de bomba 4 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31.000
40041
(40)
Modo de bomba 1 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40042
(41)
Modo de bomba 2 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40043
(42)
Modo de bomba 3 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40044
(43)
Modo de bomba 4 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40062
(61)
Estado general BITMAP 0: SBM
1: SSM
R 31.000
40068
(67)
Valor de consigna 1 UINT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
RW 31.000
40069
(68)
Valor de consigna 2 UINT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
RW 31.000
40074
(73)
Aplicación ENUM 0. Booster
1. HVAC
2. WP
3. Lift
4. FFS-Diesel
5. FFS-Electro
6. FLA
7. Clean
8. Rain
R 31.101
40075
(74)
Valor de consigna
externo
INT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
R 31.000
40076
(75)
Activar el valor de
consigna externo
BOOL RW 31.000
40077
40078
(76 77)
Número de procesos de
conexión de la
instalación
UINT32 R 31.000
40079
40080
(78 79)
Datos del cuadro sobre
horas de funcionamiento
UINT32 1h R 31.000
40081
40082
(80 81)
Ciclos de maniobras
totales de bomba 1
UINT32 R 31.000
Registro de
retención
Nombre Tipo de
datos
Escala
y unidad
Elementos Acceso Aña-
dido