Manual de instalação e funcionamento Wilo-Control SC-Booster (SC, SC-FC, SCe) 51
40035
(34)
Estado da bomba 3 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31.000
40036
(35)
Estado da bomba 4 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31.000
40041
(40)
Modo das bombas 1 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40042
(41)
Modo das bombas 2 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40043
(42)
Modo das bombas 3 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40044
(43)
Modo das bombas 4 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40062
(61)
Estado geral BITMAP 0: SBM
1: SSM
R 31.000
40068
(67)
Valor nominal 1 UINT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
RW 31.000
40069
(68)
Valor nominal 2 UINT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
RW 31.000
40074
(73)
Aplicação ENUM 0. Booster
1. HVAC
2. WP
3. Lift
4. FFS-Diesel
5. FFS-Electro
6. FLA
7. Clean
8. Rain
R 31.101
40075
(74)
Valor nominal externo INT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
R 31.000
40076
(75)
Ativar o valor nominal
externo
BOOL RW 31.000
40077 -
40078
(76-77)
Número de ativações por
instalação
UINT32 R 31.000
40079 -
40080
(78-79)
Dados dos aparelhos de
distribuição Horas de
funcionamento
UINT32 1 h R 31.000
40081 -
40082
(80-81)
Ciclos totais de arranque
da bomba 1
UINT32 R 31.000
Holding
register
Nome Tipo
de dado
Escala &
Unidade
Elementos Acesso Adicio-
nado