Monterings- og driftsveiledning Wilo-Control SC-Booster (SC, SC-FC, SCe) 51
40035
(34)
Pumpestatus 3 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31.000
40036
(35)
Pumpestatus 4 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31.000
40041
(40)
Pumpemodus 1 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40042
(41)
Pumpemodus 2 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40043
(42)
Pumpemodus 3 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40044
(43)
Pumpemodus 4 ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40062
(61)
Generell status BITMAP 0: SBM
1: SSM
R 31.000
40068
(67)
Settpunkt 1 UINT16 0,1 bar
0,1 m
0,1 K
0,1 °C
0,1 pund per
kvadrattomme
RW 31.000
40069
(68)
Settpunkt 2 UINT16 0,1 bar
0,1 m
0,1 K
0,1 °C
0,1 pund per
kvadrattomme
RW 31.000
40074
(73)
Applikasjon ENUM 0. Booster
1. HVAC
2. WP
3. Lift
4. FFS-Diesel
5. FFS-Electro
6. FLA
7. Clean
8. Rain
R 31.101
40075
(74)
Eksternt settpunkt INT16 0,1 bar
0,1 m
0,1 K
0,1 °C
0,1 pund per
kvadrattomme
R 31.000
40076
(75)
Aktiver eksternt
settpunkt
BOOL RW 31.000
40077 -
40078
(76-77)
Antall innkoblinger per
anlegg
UINT32 R 31.000
40079 -
40080
(78-79)
Styreenhetsdata
driftstimer
UINT32 1 t R 31.000
Lagrings-
register
Navn Datatype Skalering
& Enhet