Installation and operating instructions Wilo-Control SC-Booster (SC, SC-FC, SCe) 21
SCe (p-c)
SC…FC
The maximum speed of the pumps. When changed,
the parameter is adjusted by the controller so that it
remains at least 5% above the minimum frequency.
SC...FC:
80 … 100
SCe:
80 … 100
SCe (p-c)
SC…FC
The minimum speed of the pumps. When changed,
the parameter is adjusted by the controller so that it
remains at least 5 % below the maximum frequency.
SC...FC:
40 70
SCe:
15…30 … 80
SCe
SC…FC
The acceleration ramp describes the minimum
amount of time that is required to accelerate a
pump from minimum speed to maximum speed.
0.0 … 0.1 … 10.0
SCe
SC…FC
The deceleration ramp describes the minimum
amount of time that is required to reduce the speed
of a pump from maximum speed to minimum speed.
0.0 … 0.1 … 10.0
Information regarding active communication inter
-
faces
Display of currently activated field bus protocol No bus / Modbus /
BACnet / GSM /
GPRS / LON
GSM
activated
Status display of the GSM connection
(0: not available or fault; 1: OK or initialised)
- M – Modem
- S – SIM card
- P – PIN code
- N – Network connection
(0: off, 1..8: weak strong, 9: very strong)
GPRS
activated
Status display of the GPRS connection
E – Error = 1
W – Waiting = 1
S – Sending = 1
O – Transmission OK = 1
Valid until Display
Description
Parameter range
Factory setting