Initialization, Setup, and Checkout 3-55
4. Depress the Foot Switch and immediately release it. The press should make a single
stroke and stop at top dead center. Verify that the “Foot switch N/C” LED on the WPC
2000 Main Processor board turns off when the Foot Switch is depressed and that the “Foot
switch N/O” LED illuminates.
5. Set option switch 3 to ON.
6. Power down, then power back up WPC 2000 to enable the settings change. You are now
in Foot Control mode. The press should cycle to Top-stop only if the Foot Switch is held
down past the Auto Carry-up Angle.
7. Press and hold the Foot Switch through the Auto Carry-up Angle, then release the Foot
Switch. The press should complete the stroke, stopping at Top-stop.
8. Press and hold the Foot Switch again, but release it before the Auto Carry-up Angle. The
press should begin to cycle but stop immediately when the Foot Switch is released.
9. Press and hold both Run/Inch buttons. The press should complete the stroke, stopping at
Top-stop.
10. Set the Stroke Select switch to “CONT.”
11. Press the Prior Act button on the Operator Station, and, before the indicator lamp goes out,
depress and hold down the Foot Switch. The press should run as long as the Foot Switch
is depressed.
12. Release the Foot Switch. The press should complete the stroke, stopping at Top-stop.
13. Press the Prior Act button and, before the indicator lamp goes out, depress the Foot
Switch, immediately releasing it. The press should stop after a single stroke.
14. If you want to repeat testing of the Foot Switch in Continuous mode, make sure to press
the Prior Act button before attempting to initiate another stroke.
15. Go to the next applicable test.
If the Interrupted Stroke LED flashes, you must depress and hold the Run/Inch buttons on
the Operator Station to bring the press back to top dead center and clear the Interrupted
Stroke before you can operate the Foot Switch.