Fault finding and diagnosis
Greenstar 2000 – 6 721 820 552 (2021/02)
76
247 System fault boiler electronics / basic
controller
Reset burner control - factory reset.
Check electrical connections of burner control.
Replace burner control.
249 V Internal software error Restart the appliance to see if the problem re-occurs.
Check the electrical connections on the board (check for loose wires etc.).
Check the code plug, if present, is not damaged.
Replace the code plug, if present and required.
Replace the control unit (PCB).
250 V Default software error Restart the appliance to see if problem re-occurs.
Check the electrical connections on the board (check for loose wires etc.).
Check the code plug, if present, is not damaged.
Replace the code plug, if present and required.
Replace the control unit (PCB).
251 V Flash test error Restart the appliance to see if the problem re-occurs.
Check the electrical connections on the board (check for loose wires etc.).
Check the code plug, if present, is not damaged.
Replace the code plug, if present and required.
Replace the control unit (PCB).
252 V Stack overflow Restart the appliance to see if the problem re-occurs.
Check the electrical connections on the board (check for loose wires etc.).
Check the code plug, if present, is not damaged.
Replace the code plug, if present and required.
Replace the control unit (PCB).
253 V RAM test error Restart the appliance to see if the problem re-occurs.
Check the electrical connections on the board (check for loose wires etc.).
Check the code plug, if present, is not damaged.
Replace the code plug, if present and required.
Replace the control unit (PCB).
254 V Eeprom test error Restart the appliance to see if the problem re-occurs.
Check the electrical connections on the board (check for loose wires etc.).
Check the code plug, if present, is not damaged.
Replace the code plug, if present and required.
Replace the control unit (PCB).
256 V System fault boiler electronics / basic
controller
Reset control unit / burner control unit - factory reset.
Reconnect electrical connections at control unit correctly.
Replace the control unit/burner control unit.
257 System fault boiler electronics / basic
controller
Reset burner control - factory reset.
Check electrical connections of burner control.
Replace burner control.
258 V Internal watchdog error Restart the appliance to see if the problem re-occurs.
Check the electrical connections on the board (check for loose wires etc.).
Check the code plug, if present, is not damaged.
Replace the code plug, if present and required.
Replace the control unit (PCB).
259 V AD reference error Restart the appliance to see if the problem re-occurs.
Check the electrical connections on the board (check for loose wires etc.).
Check the code plug, if present, is not damaged.
Replace the code plug, if present and required.
Replace the control unit (PCB).
262 V Internal OS error Restart the appliance to see if the problem re-occurs.
Check the electrical connections on board (check for loose wires etc.).
Check the code plug, if present, is not damaged.
Replace the code plug, if present and required.
Replace the control unit (PCB).
Fault
code
Fault
category
Description Remedy