Fault finding and diagnosis
79
Greenstar 2000 – 6 721 820 552 (2021/02)
1019 Incorrect pump type detected Pump communication failure or wrong pump is fitted (non-ErP).
Check the pump communication wire is connected and has continuity.
Replace the pump for correct modulating pump.
1021 B Cylinder charging or hot water temperature
sensor faulty
Check the domestic hot water temperature sensor connected and the plug connected
to temperature sensor.
Check the resistance of the temperature sensor and replace if required.
Check the continuity of harness and replace if required.
1023 R Maximum run time including standby time
reached
Check the maintenance menu.
Reset the maintenance code via the reset menu.
1025 Return temp. sensor is faulty Not fitted on the boiler.
1037 W Outside temp. sensor faulty - heating back-
up operation active
Tip: Check the weather compensation is applicable and the menu has not been accidently
switched on in the menu.
Check the positioning of the outside weather sensor.
Check the weather sensor connections on the control board.
Check the resistance of the sensor and the continuity down the cable and replace if
required.
1068 W Outside temp. sensor or lambda probe
faulty
Check the outdoor sensor plug is connected.
Check the resistance of the sensor and replace if required.
Check the continuity of harness and replace if required.
Replace the outdoor sensor.
1073 W Short circuit of the flow temperature sensor Check the flow temperature sensor plug is connected.
Check the resistance of the flow temperature sensor and replace if required.
Check the continuity of harness and replace if required.
Replace the flow temperature sensor.
1074 W No signal from flow temperature sensor Check the flow temperature sensor plug is connected.
Check the resistance of the flow temperature sensor and replace if required.
Check the continuity of harness and replace if required.
Replace the flow temperature sensor.
Replace the PCB.
1075 W Short-circuit heat exchanger temperature
sensor
Check the temperature sensor plug is connected.
Check the resistance of sensor and replace if required.
Check the continuity of harness and replace if required.
Replace the temperature sensor.
Replace the PCB.
1076 W No signal from heat exchanger temperature
sensor
Replace the temperature sensor plug is connected.
Check the resistance of sensor and replace if required.
Check the continuity of harness and replace if required.
Replace the temperature sensor.
Replace the PCB.
2051 Internal fault Disconnect power from the system for 30 seconds.
Check and replace control unit.
Notify customer service.
2085 V Internal fault Reset the appliance.
Switch off the appliance for 30 s then turn back on.
Check the incoming mains voltage.
Check the polarity.
Replace the PCB.
2908 V System fault boiler electronics/basic
controller
Restart the appliance to see if the problem re-occurs.
If the fault remains after resetting: the burner controller (PCB) is defective and must be
replaced.
2909 System fault boiler electronics / basic
controller
If the fault persists following a reset, the burner control unit or Key (including
interconnecting leads) is faulty and must be replaced.
2910 V Fault in flue system Check the flue for obstructions and remove any found.
Check the flue integrity test.
Check for water in the sump and check the siphon operation.
Fault
code
Fault
category
Description Remedy

Table of Contents

Other manuals for Worcester GR2300iW C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester GR2300iW C and is the answer not in the manual?

Worcester GR2300iW C Specifications

General IconGeneral
BrandWorcester
ModelGR2300iW C
CategoryBoiler
LanguageEnglish

Related product manuals