Adjusting Settings in Configuration Mode
48 Freedom X 2000 - 230V Owner's Guide
Settings
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Inverter Ignition Control
01 OFF
OFF
LOT
ATO
See Description of Ignition Control Features on page 35.
LBCO Voltage
02 10.5 10.0 to 12.8
The voltage setting value can be adjusted by 0.1 increments. The
inverter is able to recover automatically at LBCO voltage + 2.0V
(default).
LBCO Shutdown Delay
Timer
03 10 0 to 300
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-s increments. When the range is from 20 to 300, the
timer setting value can be adjusted by 10-s increments.
LBCO Recovery Voltage
04 13.1 10.2 to 32.0
The range is from LBCO voltage + 0.2 to 32, adjusted by 0.1
increments. Selecting a higher value than the battery’s actual fully-
charged voltage level will disable the auto-recovery feature. You
may manually reset the inverter when the low battery cut off event
occurs.
Power Save Time
05 25 OFF, 1 to 25
The range is from 1 to 25, adjusted by 1-h increments. The next
setting after 25 is OFF.
Power Save (Load
Sensing) Mode
06 dIs
ENA (enable),
DIS (disable)
When enabled, the inverter’s “no load” loss can be reduced further
when total load is less than 25W.