VESDA-EVEP-A10-P Product Guide
44 www.xtralis.com
4.3.12 Specify Backup Battery
In the event of a mains power supply disruption, the VEP-A10-P detector runs on a backup battery located in
the external power supply (the power supply must be compliant with local fire protection codes and
standards). The size of the battery is determined by:
l local codes and standards
l the total power required by the system
l back up time required
l allowance for reduction in capacity with age
l expected temperature variations
Note: It is recommended that batteries be inspected and changed as per manufacturers specifications or
as per local codes and standards.
To facilitate the calculation of the backup battery size, a Battery Calculation Sheet is included below.
Equipment Normal loads@ 24 V DC
(Backlight off)
Full alarm load @ 24 V DC
(Backlight on)
Load (A) Qty Total Load (A) Qty Total
Detector set to Fan Speed 1 0.34 0.43
Detector set to Fan Speed 5 0.42 0.48
Other 24V Loads Total
(A)
Total
(A)
X X
Normal Hours Alarm Hours
=
Normal Capacity Alarm Capacity
Total Capacity =
Normal + Alarm
Multiply by battery
factor X1.25
Table4-3: Calculating the size of backup battery

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xtralis VESDA-E VEP-A10-P and is the answer not in the manual?

Xtralis VESDA-E VEP-A10-P Specifications

General IconGeneral
BrandXtralis
ModelVESDA-E VEP-A10-P
CategorySmoke Alarm
LanguageEnglish

Related product manuals