12.2 A: Initialization Parameters
492 YASKAWA SIEPC71061753C GA500 Technical Manual
No. Name Optimal Value
L6-01 Torque Detection Selection 1 8: UL @ RUN - Fault
L6-02 Torque Detection Level 1 2%
L6-03 Torque Detection Time 1 0.5 s
L8-05 Input Phase Loss Protection Sel 1: Enabled
L8-07 Output Phase Loss Protection Sel 1: Fault when One Phase is Lost
L8-41 High Current Alarm Selection 1: Enabled
The drive saves the parameters in Table 12.15 as User Parameters.
Table 12.15 Parameters Saved as User Parameters with the Hoist Preset
User Parameter No. Parameter No. Saved Name
A2-01 A1-02 Control Method Selection
A2-02 b1-01 Frequency Reference Selection 1
A2-03 b6-01 Dwell Reference at Start
A2-04 b6-02 Dwell Time at Start
A2-05 C1-01 Acceleration Time 1
A2-06 C1-02 Deceleration Time 1
A2-07 C6-02 Carrier Frequency Selection
A2-08 d1-01 Reference 1
A2-09 d1-02 Reference 2
A2-10 d1-03 Reference 3
A2-11 E1-08 Mid Point A Voltage
A2-12 H2-01 Term MA/MB-MC Function Selection
A2-13 L1-01 Motor Overload (oL1) Protection
A2-14 L4-01 Speed Agree Detection Level
A2-15 L6-02 Torque Detection Level 1
A2-16 L6-03 Torque Detection Time 1
7 : Crane (Traveling)
The drive automatically sets the parameters in Table 12.16 for a traveling application.
Table 12.16 Optimal Settings for Traveling Applications
No. Name Optimal Value
A1-02 Control Method Selection 0: V/f Control
b1-01 Frequency Reference Selection 1 0: Keypad
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C6-01 Normal / Heavy Duty Selection 0: Heavy Duty Rating
C6-02 Carrier Frequency Selection 2: 5.0 kHz (4.0 kHz for AOLV/PM)
d1-01 Reference 1 6.00 Hz
d1-02 Reference 2 30.00 Hz
d1-03 Reference 3 50.00 Hz
H1-05 Terminal S5 Function Selection 3: Multi-Step Speed Reference 1
H1-06 Terminal S6 Function Selection 4: Multi-Step Speed Reference 2
H2-01 Term MA/MB-MC Function Selection 37: During Frequency Output
H2-02 Terminal P1-C1 Function Selection 37: During Frequency Output
L3-04 Stall Prevention during Decel 0: Disabled
L8-05 Input Phase Loss Protection Sel 1: Enabled