19 Troubleshooting
116 YASKAWA TOEPC71061737B GA800 Drive Installation & Primary Operation
Code Name Causes Possible Solutions
The acceleration time is too short. Make sure that sudden drive acceleration does not cause the
fault.
Increase the values set in C1-01, C1-03, C1-05, or C1-07
[Acceleration Times].
Increase the value set in C2-02 [S-Curve Time @ End of Accel].
Set L3-11 = 1 [Overvoltage Suppression Select = Enabled].
The braking load is too large. Connect a dynamic braking option to the drive.
There are surge voltages in the input power supply. Connect a DC link choke to the drive.
Note:
If you turn the phase advancing capacitors ON and OFF and use
thyristor converters in the same power supply system, there can
be surge voltages that irregularly increase the input voltage.
The drive output cable or motor is shorted to ground
(the current short to ground is charging the main
circuit capacitor of the drive through the power
supply).
1. Examine the motor main circuit cable, terminals, and motor
terminal box, and then remove ground faults.
2. Re-energize the drive.
If the drive detects ov in these conditions, the speed
search-related parameters are incorrect:
During speed search
During momentary power loss recovery
When the drive starts again automatically
Examine the settings for all speed search related parameters.
Set b3-19 0 [Speed Search Restart Attempts 0 times].
Adjust b3-03 [Speed Search Deceleration Time] setting.
Do Stationary Auto-Tuning for Line-to-Line Resistance and then
set b3-24 = 1 [Speed Search Method Selection = Speed
Estimation].
The power supply voltage is too high. Decrease the power supply voltage to align with the drive rated
voltage.
The braking resistor or braking resistor unit wiring is
incorrect.
Correct wiring errors in the connection to the braking resistor or
braking resistor unit.
The encoder cable is disconnected or wired
incorrectly.
Examine for wiring errors or disconnected wires in the encoder
cable, and repair problems.
Electrical interference along the encoder cable. Isolate the encoder cable from the drive output line or a different
source of electrical interference.
Electrical interference caused a drive malfunction. Examine the control circuit lines, main circuit lines, and ground
wiring, and decrease the effects of electrical interference.
Make sure that a magnetic contactor is not the source of the
electrical interference, then use a Surge Protective Device if
necessary.
The load inertia is set incorrectly. Examine the load inertia settings with KEB, overvoltage
suppression, or stall prevention during deceleration.
Adjust L3-25 [Load Inertia Ratio] to align with the qualities of
the machine.
The Short Circuit Braking function was used in OLV/
PM control method.
Connect a braking resistor to the drive.
There is motor hunting. Adjust n1-02 [Hunting Prevention Gain Setting] settings.
Adjust n2-02 [Automatic Freq Regulator Time 1] and n2-03
[Automatic Freq Regulator Time 2] settings.
Adjust n8-45 [Speed Feedback Detection Gain] and n8-47 [Pull-
in Current Comp Filter Time] settings.
Speed search does not complete at start when you use
an induction motor in EZOLV control.
When E9-01 = 0 [Motor Type Selection = Induction (IM)], set b3-
24 = 2 [Speed Search Method Selection = Current Detection 2].
PE1, PE2 PLC Faults
The communication option detected a fault. Refer to the manual for the communication option card.
PF Input Phase Loss
There is a phase loss in the drive input power. Correct errors with the wiring for main circuit drive input power.
There is loose wiring in the drive input power
terminals.
Tighten the terminal screws to the correct tightening torque.
The drive input power voltage is changing too much. Examine the input power for problems.
Make the drive input power stable.
If the input power supply is good, examine the magnetic
contactor on the main circuit side for problems.
There is unsatisfactory balance between voltage
phases.
Examine the input power for problems.
Make the drive input power stable.
Set L8-05 = 0 [Input Phase Loss Protection Sel = Disabled].