10 Drive Start-Up Procedure
YASKAWA TOEPC71061737B GA800 Drive Installation & Primary Operation 59
Figure 10.2 Tightening Torque Display Location (Reverse side of Front Cover)
Figure 10.3 Tightening Torque Display Location (Lower Front Side of Front Cover)
■ Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire to wire the control circuit terminal block.
Use crimp ferrules on the wire ends to make the wiring procedure easier and more reliable.
Table 10.6 Control Circuit Wire Gauges and Tightening Torques
Terminal Block Terminal Screw Size
Tightening
Torque
N∙m (in∙lb)
Bare Wire Crimp Ferrule
Recommended
Gauge
mm
2
(AWG)
Applicable
Gauge
mm
2
(AWG)
Recommended
Gauge
mm
2
(AWG)
Applicable
Gauge
mm
2
(AWG)
TB1 S1 - S8, SN, SC, SP
M3
0.5 - 0.6
(4.4 - 5.3)
0.75
(18)
• Stranded wire
0.2 - 1.0
(24 - 16)
• Solid wire
0.2 - 1.5
(24 - 16)
0.5
(20)
0.25 - 0.5
(24 - 20)
TB2 M1 - M6,MA,MB,MC
TB3
+V,AC,-V,A1,A2,A3,
FM,AM,AC,MP,RP,AC
TB4
E (G),SN,HC,H1,H2,PS,
AC,D+,D-
TB5 E (G) M3.5
0.5 - 1.0
(4.4 - 8.9)
0.5 - 2
(20 - 14)
1.25
(12)
- -
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules. Refer to Table 10.7 for the recommended external
dimensions and model numbers of crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.