10 Drive Start-Up Procedure
56 YASKAWA TOEPC71061737B GA800 Drive Installation & Primary Operation
NOTICE
Damage to Equipment. The drive can fail if users frequently turn the drive ON and OFF with the MC on the power
source side to Run and Stop the drive. Incorrect operation can decrease the service life of the relay contacts and electrolytic
capacitors. If you frequently use the magnetic contactor on the power source side to Run and Stop the drive, it can cause drive
failure.
■ Input Terminals
Refer to Table 10.1 for a list of input terminals and functions.
Table 10.1 Multi-function Input Terminals
Type Terminal Name (Default) Function (Signal Level)
Digital Inputs
S1
MFDI selection 1
(ON: Forward run OFF: Stop)
• Photocoupler
• 24 V, 6 mA
Note:
Install the wire jumpers between terminals SC-SP and SC-SN to set the MFDI power supply
(sinking/sourcing mode or internal/external power supply).
• Sinking Mode: Install a jumper between terminals SC and SP.
NOTICE
Damage to Equipment. Do not close the circuit
between terminals SC-SN. If you close the circuits terminals SC-SP
and terminals SC-SN, it will cause damage to the drive.
• Sourcing Mode: Install a jumper between terminals SC and SN.
NOTICE
Damage to Equipment. Do not close the circuit
between terminals SC-SP. If you close the circuits terminals SC-SP
and terminals SC-SN, it will cause damage to the drive.
• External power supply: No jumper necessary between terminals SC-SN and terminals SC-SP.
S2
MFDI selection 2
(ON: Reverse run OFF: Stop)
S3
MFDI selection 3
(External fault (N.O.))
S4
MFDI selection 4
(Fault reset)
S5
MFDI selection 5
(Multi-step speed reference 1)
S6
MFDI selection 6
(Multi-step speed reference 2)
S7
MFDI selection 7
(Jog command)
S8
MFDI selection 8
(Baseblock command (N.O.))
SN MFDI power supply 0 V
MFDI power supply, 24 V (maximum 150 mA)
NOTICE
Do not close the circuit between terminals SP-SN. A
closed circuit between these terminals will cause damage to the drive.
SC MFDI selection common
SP MFDI power supply +24 Vdc
Safe Disable
Input
H1 Safe Disable input 1
Remove the jumper between terminals H1-HC and H2-HC to use the Safe Disable input.
• 24 V, 6 mA
• ON: Normal operation
• OFF: Coasting motor
• Internal impedance 4.7 kΩ
• OFF Minimum OFF time of 2 ms.
H2 Safe Disable input 2
HC Safe Disable function common
Safe Disable function common
NOTICE
Do not close the circuit between terminals HC and SN.
A closed circuit between these terminals will cause damage to the drive.