12 UL Standards
80 YASKAWA TOEPC71061737B GA800 Drive Installation & Primary Operation
Drive Model
Fuse
Manufacturer: Bussmann
Model Quantity
2138 FWH-300A 2
2169 FWH-350A 2
2211 FWH-450A 2
2257 FWH-600A 2
2313 FWH-800A 2
2360
FWH-1000A 2
2415
*1 Yaskawa recommends a fuse with a larger rated current for cyclic load applications that frequently approach 150% overload.
Table 12.5 Recommended DC Input Fuse (Three-Phase 400 V Class)
Drive Model
Fuse
Manufacturer: Bussmann
Model Quantity
4002
FWP-50B 24004
4005
4007
FWP-60B 24009
4012
4018 FWP-80B 2
4023 FWP-90B 2
4031 FWP-150A 2
4038
FWP-200A 2
4044
4060 FWP-225A 2
4075 FWP-250A 2
4089
FWP-300A 2
4103
4140 FWP-350A 2
4168 FWP-450A 2
4208 FWP-600A 2
4250 FWP-700A 2
4302 FWP-800A 2
4371
Not applicable
4414
4477
4568
4605
4720