Parameter List
3
3.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting 303
No.
*1
Name Unit Default
- Drive Model - T250 T302 T371 T414
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 01A7 01A8 01A9 01AA
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
150
(110)
200
(150)
200
(150)
250
(185)
250
(185)
300
(220)
300
(220)
350
(260)
L8-09
Output Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 30 30 30 30 30 30 100 100
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.646 0.673 0.673 0.777 0.777 0.864 0.864 0.91
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - T477 T568 T605 T720
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 01AC 01AD 01AE 01AF
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
350
(260)
400
(300)
400
(300)
450
(335)
450
(335)
500
(370)
500
(370)
600
(450)
b3-04
V/f Gain
during Speed
Search
% 60 60 60 60 60 60 60 60
b3-06
Speed
Estimation
Current Level
1
- 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Speed
Estimation
ACR P Gain
- 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
b8-04
Energy Saving
Coefficient
Value
- 27.13 21.76 21.76 21.76 21.76 23.84 21.76 23.84
C5-17
(C5-37)
Motor Inertia kgm
2
4.10 6.50 6.50 11.00 11.00 12.00 11.00 12.00
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 370 500 500 500 500 650 500 650