Select the value to be set in H1-oo from a combination of any of the following three conditions:
Signal input level from peripheral devices (N.O., N.C.)
External fault detection method
Operation after external fault detection
An “On-Delay” timer will be applied to the external fault if it is “Normally Open” and an “Off-Delay” timer will be applied
to the external fault if it is “Normally Closed”.
If the external fault is set to “During Run”, the time delay will start after the Run command is received.
Refer to Figure 5.46 to Figure 5.48 for details.
Table 5.21 shows the relationship between the conditions and the value set to H1-oo:
Terminal statuses, detection conditions, and stopping methods marked with an “O” are applicable to the corresponding settings.
Table 5.21 Stopping Method for External Fault
Setting
Terminal Status
<1>
Detection Conditions
<2>
Stopping Method
N.O. N.C.
Always
Detected
Detected
during Run
only
Ramp to Stop
(fault)
Coast to Stop
(fault)
Fast Stop
(fault)
Alarm Only
(continue
running)
20 O O O
21 O O O
22 O O O
23 O O O
24 O O O
25 O O O
26 O O O
27 O O O
28 O O O
29 O O O
2A O O O
2B O O O
2C O O O
2D O O O
2E O O O
2F O O O
<1> Determine the terminal status for each fault, i.e., whether the terminal is normally open or normally closed.
<2> Determine whether detection for each fault should be enabled only during run or always detected.
External Pump Fault (or Alarm) N.O. Always Detected
Pump Fault
Digital Input
(H1-0= 2)
EF☐ Pump
Fault or Alarm
EF☐ Delay Time
EF☐ Delay
Time
H1-2
H1-2
Closed
Open
Figure 5.46 External Pump Fault and Alarm N.O. Always Detected
5.7 H: Terminal Functions
168
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual