H2-oo
Setting
Function LCD Display Description Page
9
Frequency reference
source
Ref Source
Open: External Reference 1 or 2 supplies the frequency reference
(set in b1-01 or b1-15).
Closed: Digital operator supplies the frequency reference.
177
A HAND mode Hand Mode
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Pump is in HAND Mode operation.
177
B
Torque detection 1
(N.O.)
Trq Det 1 N.O.
Closed: An overtorque or undertorque situation has been detected.
177
C
Frequency reference
loss
Loss of Ref
Closed: Analog frequency reference has been lost.
Frequency reference loss is detected when the frequency reference drops below
10% of the reference within 400 ms.
177
D Braking resistor fault DB Overheat Closed: Braking resistor or transistor is overheated or faulted out. 177
E Fault Fault Closed: Fault occurred. 177
F Through mode Not Used Set this value when using the terminal in the pass-through mode. 177
10 Minor fault Minor Fault
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their
expected life span.
177
11
Fault reset command
active
Reset Cmd Active
Closed: A command has been entered to clear a fault via the input terminals or
from the serial network.
177
12 Timer output Timer Output Closed: Timer output. 177
13 Speed agree 2 Fref/Fout Agree2 Closed: When drive output frequency equals the frequency reference ±L4-04. 178
14 User-set speed agree 2 Fref/Set Agree 2 Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04. 178
15 Frequency detection 3 Freq Detect 3
Closed: When the drive output frequency is less than or equal to the value in
L4-03 ±L4-04.
178
16 Frequency detection 4 Freq Detect 4
Closed: When the output frequency is greater than or equal to the value in
L4-03 ±L4-04.
179
17
Torque detection 1
(N.C.)
Trq Det 1 N.C.
Open: Overtorque or undertorque has been detected.
177
18
Torque detection 2
(N.O.)
Trq Det 2 N.O.
Closed: Overtorque or undertorque has been detected.
19
Torque detection 2
(N.C.)
Trq Det 2 N.C.
Open: Overtorque or undertorque has been detected.
177
1A During reverse Reverse Dir Closed: Drive is running in the reverse direction. 179
1B
During baseblock
(N.C.)
BaseBlk 2
Open: Drive has entered the baseblock state (no output voltage).
180
1E Restart enabled Dur Flt Restart Closed: Automatic restart is performed 180
1F
Motor overload alarm
(oL1)
Overload (OL1)
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers
this alarm.
180
20
Drive overheat pre-
alarm (oH)
OH Prealarm
Closed: Heatsink temperature exceeds the parameter L8-02 value.
180
22
Mechanical weakening
detection
MechFatigue(OL5)
Closed: Mechanical weakening detected.
180
2F Maintenance period Maintenance
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay
may require maintenance.
180
37
During frequency
output
During RUN 2
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial
Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is
not being performed).
180
38 Drive enabled Drive Enable
Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A)
180
39 Watt hour pulse output Watt-hour Pulse
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate
the kWh count.
180
3D During speed search During SpdSrch Closed: Speed Search is being executed. 181
3E PID feedback low PID Feedback Low Closed: PID feedback level is too low. 181
3F PID feedback high PID FeedbackHigh Closed: The PID feedback level is too high. 181
4A During KEB Ride-Thru During KEB Closed: KEB Ride-Thru is being performed. 181
4C During fast stop During Fast Stop
Closed: A Fast Stop command has been entered from the operator or input
terminals.
181
4D oH Pre-alarm time limit OH Pre-Alarm Closed: oH pre-alarm time limit has passed. 181
B.8 H Parameters: Multi-Function Terminals
340