No.
(Addr.
Hex)
Name LCD Display Description Values Page
b5-11
(01AF)
PID Output Reverse
Selection
Output Rev Sel
0: 0 limit
1: Reverse
0: Negative PID output triggers zero limit.
1: Rotation direction reverses with negative PID output.
Note: When using setting 1, make sure reverse
operation is permitted by b1-04.
Default: 0
Range: 0, 1
–
b5-12
(01B0)
Feedback Loss 4 to 20
mA Detection Selection
Fdbk 4-20mA Det
0: Disabled
1: Alarm only
2: Fault
3: Run At b5-13
Performs a 4 to 20 mA wire break detection on the analog input
that is programmed for PID feedback.
0: Disabled
1: Alarm only
2: Fault
3: Run at b5-13
Default: 2
Range: 0 to 3
–
b5-13
(01B1)
Feedback Loss Goto
Frequency
FdbkLossGotoFreq
Sets the speed at which the drive will run if a 4 to 20 mA wire
break is detected on the PID Feedback and when b5-12 is set to
3 (Run at b5-13).
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
–
b5-14
(01B2)
Feedback Loss of Prime
Level
FdbkLoss LOP Lvl
Detects loss of prime in the pump when a wire break condition
has occurred.
When the measured quantity determined by P1-18 (output
current, kilowatts, or power) drops below this level for the time
set in P1-20 and the output frequency is at the level set in b5-13,
a “Loss of Prime” condition occurs.
The drive responds to the “Loss of Prime” condition depending
on the setting of P1-22, Loss of Prime Selection.
Default: 0.0 A
<1>
Min.: 0.0
Max.: 1000.0
–
b5-17
(01B5)
PID Accel/Decel Time PID Acc/Dec Time
Sets the acceleration and deceleration time to PID setpoint. Default: 0.0 s
Min.: 0.0
Max.: 6000.0
–
b5-34
(019F)
PID Output Lower Limit PID Out Low Lim
Sets the minimum output possible from the PID controller as a
percentage of the maximum output frequency.
Default: 0.00%
Min.: -100.00
Max.: 100.00
–
b5-35
(01A0)
PID Input Limit PID Input Limit
Limits the PID control input (deviation signal) as a percentage
of the maximum output frequency. Acts as a bipolar limit.
Default:
1000.0%
Min.: 0.0
Max.: 1000.0
–
b5-39
(01FF)
PID Setpoint Display
Digits
PID UsrDspDigits
0: No Dec (XXXXX)
1: 1 Dec (XXXX.X)
2: 2 Dec (XXX.XX)
3: 3 Dec (XX.XXX)
0: No decimal places
1: One decimal place
2: Two decimal places
3: Three decimal places
Default: 1
Range: 0 to 3
–
b5-40
(017F)
Frequency Reference
Monitor Content during
PID
Fref Mon Sel@PID
0: Fref Mon w PID
1: Fref Mon w/o PID
0: Display the frequency reference (U1-01) after PID
compensation has been added.
1: Display the frequency reference (U1-01) before PID
compensation has been added.
Default: 0
Range: 0, 1
–
b5-41
(0160)
PI Output 2 Unit
Selection
PI Out2 Unit Sel
0: No Unit
1: PSI :lb/SqrInch
2: Pa:Pascals
3: Bar:Bar
4: "WC: InchOfWater
5: "Hg:Inch Mercury
6: ft: feet
7: m: meters
8: °F:DegFarenheit
9: °C:DegCelsius
10: %: Percent
25: Flow (use P6-04)
0: No Unit
1: Pounds per square inch
2: Pascals
3: Bar
4: Inch of Water
5: Inch of Mercury
6: Feet
7: Meters
8: Degrees Fahrenheit
9: Degrees Celsius
10: Percent
25: Flow (use P6-04)
Default: 0
Range: 0 to 10;
25
–
b5-42
(0161)
PI Output 2 Calculation
Mode
PI Out2 Calc Mode
0: Linear
1: Square root
2: 1/f2
3: 1/f3
0: Linear - the monitor displays PID output
1: Square root - the monitor displays square root PID output
2: Quadratic - the monitor displays 1/(PID output)
2
3: Cubic - the monitor displays 1/(PID output)
3
Note: Used for U5-14 and U5-15 only.
Default: 0
Range: 0 to 3
–
b5-43
(0162)
PI Output 2 Monitor
Max Upper 4 Digits
PI Out2 MonMax U
Sets the upper 4 digits of the maximum monitor value.
Used with b5-44 to set maximum monitor value of U5-14 and
U5-15 at maximum frequency.
Note: Used for U5-14 and U5-15 only.
Default: 0
Min.: 0
Max.: 9999
–