Loading...
No.
(Addr.
Hex)
Name LCD Display Description Values Page
F6-51
(03C2)
DeviceNet
Communication Speed
DN Baud Rate
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Set from Network
4: Auto Detect
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Adjustable from network
4: Detect automatically
Default: 4
Range: 0 to 4
F6-52
(03C3)
DeviceNet PCA Setting DN PCA Selection
Sets the format of the data set from the DeviceNet master to the
drive.
Default: 21
Min.: 0
Max.: 255
F6-53
(03C4)
DeviceNet PPA Setting DN PPA Selection
Sets the format of the data set from the drive to the DeviceNet
master.
Default: 71
Min.: 0
Max.: 255
F6-54
(03C5)
DeviceNet Idle Mode
Fault Detection
DN Idle Flt Det
0: Stop
1: Ignore
0: Enabled
1: Disabled, no fault detection
Default: 0
Range: 0, 1
F6-55
(03C6)
DeviceNet Baud Rate
Monitor
DN BAUD RATE
MEM
0: 125 kbps
1: 250 kbps
2: 500 kbps
Verifies the baud rate running on the network.
0: 125 kbps
1: 250 kbps
2: 500 kbps
Default: 0
Range: 0 to 2
F6-56
(03D7)
DeviceNet Speed
Scaling
DN Speed Scale
Sets the scaling factor for the speed monitor in DeviceNet. Default: 0
Min.: -15
Max.: 15
F6-57
(03D8)
DeviceNet Current
Scaling
DN Current Scale
Sets the scaling factor for the output current monitor in
DeviceNet.
Default: 0
Min.: -15
Max.: 15
F6-58
(03D9)
DeviceNet Torque
Scaling
DN Torque Scale
Sets the scaling factor for the torque monitor in DeviceNet. Default: 0
Min.: -15
Max.: 15
F6-59
(03DA)
DeviceNet Power
Scaling
DN Power Scale
Sets the scaling factor for the power monitor in DeviceNet. Default: 0
Min.: -15
Max.: 15
F6-60
(03DB)
DeviceNet Voltage
Scaling
DN Voltage Scale
Sets the scaling factor for the voltage monitor in DeviceNet. Default: 0
Min.: -15
Max.: 15
F6-61
(03DC)
DeviceNet Time
Scaling
DN Time Scale
Sets the scaling factor for the time monitor in DeviceNet. Default: 0
Min.: -15
Max.: 15
F6-62
(03DD)
DeviceNet Heartbeat
Interval
DN Heart Beat
Sets the heartbeat interval for DeviceNet communications. Default: 0
Min.: 0
Max.: 10
F6-63
(03DE)
DeviceNet Network
MAC ID
DN MAC ID MEM
Saves and monitors settings 0 to 63 of F6-50 (DeviceNet MAC
Address).
Default: 63
Min.: 0
Max.: 63
F6-64 to
F6-71
(03DF to
03C8)
Dynamic I/O Assembly
Parameters
Dynamic I/O Assembly Parameters
F7-01
(03E5)
<2>
IP Address 1
IP Address 1
Sets the most significant octet of network static IP address.
Default: 192
Range: 0 to 255
F7-02
(03E6)
<2>
IP Address 2
IP Address 2
Sets the second most significant octet of network static IP
address.
Default: 168
Range: 0 to 255
F7-03
(03E7)
<2>
IP Address 3
IP Address 3
Sets the third most significant octet of network static IP address.
Default: 1
Range: 0 to 255
F7-04
(03E8)
<2>
IP Address 4
IP Address 4
Sets the fourth most significant octet of network static IP
address.
Default: 20
Range: 0 to 255
F7-05
(03E9)
Subnet Mask 1 Subnet Mask 1 Sets the most significant octet of network static Subnet Mask.
Default: 255
Range: 0 to 255
B.6 F: Options
274
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide

Table of Contents

Other manuals for YASKAWA iQpump1000