No.
(Addr.
Hex)
Name LCD Display Description Values Page
F7-06
(03EA)
Subnet Mask 2 Subnet Mask 2
Sets the second most significant octet of network static Subnet
Mask.
Default: 255
Range: 0 to 255
F7-07
(03EB)
Subnet Mask 3 Subnet Mask 3
Sets the third most significant octet of network static Subnet
Mask.
Default: 255
Range: 0 to 255
F7-08
(03EC)
Subnet Mask 4 Subnet Mask 4
Sets the fourth most significant octet of network static Subnet
Mask.
Default: 0
Range: 0 to 255
F7-09
(03ED)
Gateway Address 1 Gateway IP Add 1 Sets the most significant octet of network Gateway address.
Default: 192
Range: 0 to 255
F7-10
(03EE)
Gateway Address 2 Gateway IP Add 2
Sets the second most significant octet of network Gateway
address.
Default: 168
Range: 0 to 255
F7-11
(03EF)
Gateway Address 3 Gateway IP Add 3
Sets the third most significant octet of network Gateway
address.
Default: 1
Range: 0 to 255
F7-12
(03E0)
Gateway Address 4 Gateway IP Add 4
Sets the fourth most significant octet of network Gateway
address.
Default: 1
Range: 0 to 255
F7-13
(03F1)
Address Mode at Startup
IP Add Mode Sel
0: User Defined
1: BOOTP
2: DHCP
Select the option address setting method
0: Static
<3>
1: BOOTP
2: DHCP
Default: 2
Range: 0 to 2
F7-14
(03F2)
Duplex Mode Selection
Duplex Select
0: Half Duplex
1: Auto Negotiate
2: Full Duplex
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
Default: 1
Range: 0 to 2
F7-15
(03F3)
Communication Speed
Selection
Baud Rate
10: 10 Mbps
100: 100 Mbps
Sets the communication speed
10: 10 Mbps
100: 100 Mbps
Default: 10
Range: 10, 100
F7-16
(03F4)
Communication Loss
Timeout
CommLoss Tout
Sets the timeout value for communication loss detection in
tenths of a second. A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0
Min.: 0
Max.: 300
F7-17
(03F5)
EtherNet/IP Speed
Scaling Factor
EN Speed Scale
Sets the scaling factor for the speed monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-18
(03F6)
EtherNet/IP Current
Scaling Factor
EN Current Scale
Sets the scaling factor for the output current monitor in
EtherNet/IP Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-19
(03F7)
EtherNet/IP Torque
Scaling Factor
EN Torque Scale
Sets the scaling factor for the torque monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-20
(03F8)
EtherNet/IP Power
Scaling Factor
EN Power Scale
Sets the scaling factor for the power monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-21
(03F9)
EtherNet/IP Voltage
Scaling Factor
EN Voltage Scale
Sets the scaling factor for the voltage monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-22
(03FA)
EtherNet/IP Time
Scaling
EN Time Scale
Sets the scaling factor for the time monitor in EtherNet/IP Class
ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-23 to
F7-32
(03FB to
0374)
Dynamic Output
Assembly Parameters
Parameters used in Output Assembly 116. Each parameter
contains a MEMOBUS/Modbus address. The value received for
Output Assembly 116 will be written to this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus address
value of 0 means that the value received for Output Assembly
116 will not be written to any MEMOBUS/Modbus register.
Default: 0
F7-33 to
F7-42
(0375 to
037E)
Dynamic Input
Assembly Parameters
Parameters used in Input Assembly 166. Each parameter
contains a MEMOBUS/Modbus address. The value sent for
Input Assembly 166 will be read from this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus address
value of 0 means that the value sent for Input Assembly 166 is
not defined by the user, therefore the option default register
value will be returned.
Default: 0
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Cycle power for setting changes to take effect.
<3> If F7-13 is set to 0, all IP addresses (F7-01 to F7-04) must be unique.