n
Three-Phase 600 V Class
Table 3.4 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0003
5A0004
5A0006
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
–, +1, +2 – 14 to 10
B1, B2 – 14 to 10
10 14 to 10
5A0009
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
–, +1, +2 – 14 to 10
B1, B2 – 14 to 10
10 12 to 10
5A0011
R/L1, S/L2, T/L3 10 14 to 6
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 6
–, +1, +2 – 14 to 6
B1, B2 – 14 to 10
8 12 to 8 M5
2 to 2.5
(17.7 to 22.1)
5A0017
R/L1, S/L2, T/L3 10 10 to 6
M5
2 to 2.5
(17.7 to 22.1)
U/T1, V/T2, W/T3 10 10 to 6
–, +1, +2 – 10 to 6
B1, B2 – 10 to 8
8 12 to 8 M6
4 to 6
(35.4 to 53.1)
5A0022
R/L1, S/L2, T/L3 8 10 to 6
M5
2 to 2.5
(17.7 to 22.1)
U/T1, V/T2, W/T3 10 10 to 6
–, +1, +2 – 10 to 6
B1, B2 – 10 to 8
8 10 to 6 M6
4 to 6
(35.4 to 53.1)
5A0027
5A0032
R/L1, S/L2, T/L3 6 6 to 4
M6
4 to 6
(35.4 to 53.1)
U/T1, V/T2, W/T3 6 6 to 4
–, +1, +2 – 6 to 4
B1, B2 – 10 to 8 M5
2 to 2.5
(17.7 to 22.1)
6 10 to 6 M6
4 to 6
(35.4 to 53.1)
5A0041
R/L1, S/L2, T/L3 6 10 to 3
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 6 10 to 3
–, +1 – 6 to 1
B1, B2 – 12 to 3
6 6
5A0052
R/L1, S/L2, T/L3 4 10 to 3
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 6 10 to 3
–, +1 – 6 to 1
B1, B2 – 8 to 3
6 6
5A0062
R/L1, S/L2, T/L3 4 10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 4 10 to 4/0
–, +1 – 4 to 4/0
+3 – 6 to 4/0
4 4
3.6 Main Circuit Wiring
92
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide