EasyManua.ls Logo

YASKAWA iQpump1000 - Standard Connection Diagram

YASKAWA iQpump1000
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
n
Three-Phase 600 V Class
Table 3.4 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0003
5A0004
5A0006
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
–, +1, +2 14 to 10
B1, B2 14 to 10
10 14 to 10
5A0009
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
–, +1, +2 14 to 10
B1, B2 14 to 10
10 12 to 10
5A0011
R/L1, S/L2, T/L3 10 14 to 6
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 6
–, +1, +2 14 to 6
B1, B2 14 to 10
8 12 to 8 M5
2 to 2.5
(17.7 to 22.1)
5A0017
R/L1, S/L2, T/L3 10 10 to 6
M5
2 to 2.5
(17.7 to 22.1)
U/T1, V/T2, W/T3 10 10 to 6
–, +1, +2 10 to 6
B1, B2 10 to 8
8 12 to 8 M6
4 to 6
(35.4 to 53.1)
5A0022
R/L1, S/L2, T/L3 8 10 to 6
M5
2 to 2.5
(17.7 to 22.1)
U/T1, V/T2, W/T3 10 10 to 6
–, +1, +2 10 to 6
B1, B2 10 to 8
8 10 to 6 M6
4 to 6
(35.4 to 53.1)
5A0027
5A0032
R/L1, S/L2, T/L3 6 6 to 4
M6
4 to 6
(35.4 to 53.1)
U/T1, V/T2, W/T3 6 6 to 4
–, +1, +2 6 to 4
B1, B2 10 to 8 M5
2 to 2.5
(17.7 to 22.1)
6 10 to 6 M6
4 to 6
(35.4 to 53.1)
5A0041
R/L1, S/L2, T/L3 6 10 to 3
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 6 10 to 3
–, +1 6 to 1
B1, B2 12 to 3
6 6
5A0052
R/L1, S/L2, T/L3 4 10 to 3
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 6 10 to 3
–, +1 6 to 1
B1, B2 8 to 3
6 6
5A0062
R/L1, S/L2, T/L3 4 10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 4 10 to 4/0
–, +1 4 to 4/0
+3 6 to 4/0
4 4
3.6 Main Circuit Wiring
92
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide