EasyManuals Logo

YASKAWA Varispeed E7 User Manual

YASKAWA Varispeed E7
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #101 background imageLoading...
Page #101 background image
5-14
Speed Search: b3
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Regis-
ter
Page
b3-01
Speed search
selection (current
detection or speed
calculation)
Enables/disables the speed search
function for the RUN command and
sets the speed search method.
0:Disabled, speed calculation
1: Enabled, speed calculation
2: Disabled, current detection
3: Enabled, current detection
Speed Calculation:
When the search is started, the
motor speed is calculated and
acceleration/deceleration is
performed from the calculated
speed to the specified frequency
(motor direction is also searched).
Current Detection:
The speed search is started from
the frequency when power was
momentarily lost and the
maximum frequency, and the
speed is detected at the search
current level.
0 to 3 2 No A 191H 6-39
b3-02
Speed search
operating current
(current detection)
Sets the speed search operation cur-
rent as a percentage, taking the
Inverter rated current as 100%.
Usually not necessary to set. When
restarting is not possible with the
factory settings, reduce the value.
0 to
200
120% No A 192H 6-39
b3-03
Speed search
deceleration time
(current detection)
Sets the output frequency decelera-
tion time during speed search in 1-
second units.
Sets the time for deceleration from
the maximum output frequency to
the minimum output frequency.
0.1 to
10.0
2.0 s No A 193H 6-39
b3-05
Speed search wait
time (current
detection or speed
calculation)
When a speed search is performed
after recovering from a momentary
power loss, the search operation is
delayed for the time set here.
If e.g. a contactor is used at the out-
put side of the inverter set this con-
stant to the contactor delay time or
more.
0.0 to
20.0
0.2 s No A 195H 6-39
b3-14
Bi-directional
speed search
selection
Can be used to turn off the bi-direc-
tional capabilities of the speed cal-
culation form of speed search.
Then speed search will only be per-
formed in the last known direction.
0: Disabled
1: Enabled
0 or 1 1 No A 19EH 6-39
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Other manuals for YASKAWA Varispeed E7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed E7 and is the answer not in the manual?

YASKAWA Varispeed E7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed E7
CategoryDC Drives
LanguageEnglish

Related product manuals