5-30
Multi-function Analog Outputs: H4
* An analog output signal of 4 - 20 mA requiers an optional terminal board for current output.
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
H4-01
Monitor selection
(terminal FM)
Sets the number of the monitor item
to be output (U1-) at terminal
FM.
1 to 53 2 No A 41DH 6-66
H4-02
Gain (terminal
FM)
Sets the multi-function analog out-
put 1 (terminal FM) gain.
Sets the percentage of the monitor
item that is equal to 10V output at
terminal FM. Note that the maxi-
mum output voltage is 10V.
0 to
1000.0
%
100% Yes Q 41EH 6-66
H4-03
Bias (terminal
FM)
Sets the multi-function analog out-
put 1 (terminal FM) bias.
Sets the percentage of the monitor
item that is equal to 0V output at
terminal FM.
The maximum output from the ter-
minal is 10 V.
-110 to
+110%
0.0% Yes A 41FH 6-66
H4-04
Monitor selection
(terminal AM)
Sets the number of the monitor item
to be output (U1-) at terminal
AM.
1 to 53 8 No A 420H 6-66
H4-05
Gain (terminal
AM)
Set the multi-function analog out-
put 2 (terminal AM) gain.
Sets the percentage of the monitor
item that is equal to 10V output at
terminal AM. Note that the maxi-
mum output voltage is 10V.
0 to
1000.0
%
50.0% Yes Q 421H 6-66
H4-06
Bias (terminal
AM)
Sets the multi-function analog out-
put 2 (terminal AM) bias.
Sets the percentage of the monitor
item that is equal to 0V output at
terminal AM.
The maximum output from the ter-
minal is 10 V.
-110.0
to
+110.0
%
0.0% Yes A 422H 6-66
H4-07
Analog output 1
signal level selec-
tion
Sets the signal output level for
multi-function output 1 (terminal
FM)
0: 0 to +10 V output
2: 4 – 20 mA*
0 or 2 0 No A 423H 6-66
H4-08
Analog output 2
signal level selec-
tion
Sets the signal output level for
multi-function output 2 (terminal
AM)
0: 0 to +10 V output
2: 4 – 20 mA*
0 or 2 0 No A 424H 6-66