User Constant Tables
5-41
Copy Function: o3
User constants for the copy function are shown in the following table.
o2-07
Cumulative oper-
ation time setting
Sets the cumulative operation time
in hour units.
Operation time is calculated from
the set values.
0 to
65535
0 hr No A 50BH 6-102
o2-08
Cumulative oper-
ation time selec-
tion
0: Cumulative time when the
Inverter power is on. (All time
while the Inverter power is on is
accumulated.)
1: Cumulative Inverter run time.
(Only Inverter output time is
accumulated.)
0 or 1 0 No A 50CH 6-102
o2-09 Initialize Mode
2: Europe
5: PV-E Spec.
2 or 5 2 No A 50DH 6-102
o2-10
Fan operation
time setting
Set the initial value of the fan oper-
ation time.
The operation time accumulates
from the set value.
0 to
65535
0 hr No A 50EH 6-102
o2-12
Fault trace initial-
ize
0: Disable
1: Initialize (= zero clear) after set-
ting ”1“ o2-12 will be returned to
”0“
0 or 1 0 No A 511H 6-102
o2-14
Energy monitor
initialize
Resets the monitor parameters
U1-24 and U1-30 back to zero.
0: No change
1: Reset to zero
0 or 1 0 No A 512H 6-102
o2-15
HAND Key func-
tion selection
If set to 0 the HAND button on the
digital operator is disabled and the
drive will not enter the HAND
mode and start to run when the
HAND button is pressed.
0: HAND button disabled
1: HAND button enabled
0 or 1 1 No A 513H 6-102
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
o3-01
Copy function
selection
0: Normal operation
1: READ (Inverter to Operator)
2: COPY (Operator to Inverter)
3: Verify (compare)
0 to 3 0 No A 515H 6-105
o3-02
Read permission
selection
0: READ prohibited
1: READ permitted
0 or 1 0 No A 516H 6-105
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page