6-46
Auto Restart External Outputs
To output auto restart signals externally, set H2-01 or H2-02 (multi-function contact output terminals M1-M2
or M3-M4 function selection) to 1E (auto restart).
Related Constants
Application Precautions
The number of auto restarts counter is reset under the following conditions:
After auto restart, normal operation has continued for 10 minutes.
After the protection operation has been performed and an error reset has been input.
After the power supply is turned OFF, and then ON again.
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
L5-01 Number of auto restart attempts
Sets the number of auto restart attempts.
Automatically restarts after a fault and conducts a speed
search from the run frequency.
0 to 10 0 No A
L5-02 Auto restart operation selection
Sets whether a fault contact output is activated during
fault restart.
0: Not output (Fault contact is not activated.)
1: Output (Fault contact is activated.)
0 or 1 0 No A
L5-03 Fault Retry Time Sets the maximum time a restart is tried.
0.5 to
180.0
10.0 s No A