5
-6
E1-04
Max.
output
frequency
(FMAX)
40.0 to
400.0
*7
60.0 Hz
*4
NoQQQQQ303H
Max
Frequency
E1-05
Max.
voltage
(VMAX)
0.0 to
255.0
*3
200.0
V
*3*4
NoQQQQQ304H
Max
Voltage
E1-06
Base
frequency
(FA)
0.0 to
400.0
*7
60.0 Hz
*4
NoQQQQQ305H
Base
Frequency
E1-09
Min.
output
frequency
(FMIN)
0.0 to
400.0
*7
0.5 Hz
*4
NoQQQAQ308H
Min
Frequency
E1-13
Base
voltage
(VBASE)
Change this setting only when making
advanced adjustments for V/f in the
fixed outputs area. Normally, there is
no need to make these settings.
0.0 to
255.0
*3
0.0 V
*5
NoAAQQQ30CH
Base
Voltage
E2-01
Motor
rated
current
Set the motor rated current in amps.
This set value becomes the base value
for motor protection, torque limit, and
torque control. It is set automatically
when using autotuning.
0.32 to
6.40
*6
1.90 A
*2
NoQQQQQ30EH
Motor
Rated FLA
E2-04
Number of
motor
poles
Set the number of motor poles. The
value is set automatically during auto-
tuning.
2 to 48 4 poles No No Q No Q Q 311H
Number of
Poles
E2-11
Motor
rated
output
Set the output of the motor in units of
0.01kW. This constant is automatically
set during autotuning.
0.00 to
650.00
0.40
*8
NoQQQQQ318H
Mtr Rated
Power
F1-01
PG
constant
Set the number of pulses per rotation
for the PG (pulse generator or
encoder) being used. (Do not set as a
multiple.)
0 to
60000
600 No No Q No Q No 380H
PG Pulses/
Rev
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
-loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
Output voltage (V)
Frequency
(Hz)
VMAX
(E1-05)
VMIN
(E1-10)
FMIN
(E1-09)
FA
(E1-06)
FMAX
(E1-04)
VBASE
(E1-13)
TOE-S616-60.1.book 6 ページ 2017年8月4日 金曜日 午後3時41分