EasyManuals Logo

YASKAWA Varispeed G7 Series User Manual

YASKAWA Varispeed G7 Series
541 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #146 background imageLoading...
Page #146 background image
5
-14
Speed Search: b3
User constants for the speed search are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
b3-01
Speed
search
selection
(current
detection or
speed calcu-
lation)
Enables/disables the speed
search function for the Run
Command and sets the speed
search method.
0: Disabled, speed calculation
1: Enabled, speed calculation
2: Disabled, current detection
3: Enabled, current detection
Speed Calculation:
When the search is started, the
motor speed is calculated and
acceleration/deceleration is
performed from the calculated
speed to the specified
frequency (motor direction is
also searched).
Current Detection:
The speed search is started
from the frequency when
power was momentarily lost
and the maximum frequency,
and the speed is detected at
the search current level.
0 to 3
2
*1
No A A A No A 191H 6-66
SpdSrch at
Start
b3-02
Speed
search oper-
ating current
(current
detection)
Sets the speed search operation
current as a percentage, taking
the Inverter rated current as
100%.
Not usually necessary to set.
When restarting is not possible
with the factory settings,
reduce the value.
0 to
200
100%
*1
No A No A No A 192H 6-66
SpdSrch
Current
b3-03
Speed
search
decelera-
tion time
(current
detection)
Sets the output frequency
deceleration time during speed
search in 1-second units.
Set the time for deceleration
from the maximum output fre-
quency to the minimum output
frequency.
0.1 to
10.0
2.0 s No A No A No No 193H 6-66
SpdSrch
Dec Time
b3-05
Speed
search wait
time (cur-
rent detec-
tion or
speed calcu-
lation)
Sets the magnetic contactor
operating delay time when
there is a magnetic contactor
on the output side of the
Inverter. When a speed search
is performed after recovering
from a momentary power loss,
the search operation is delayed
by the time set here.
0.0 to
20.0
0.2 s No A A A A A 195H 6-66
Search
Delay
TOE-S616-60.1.book 14 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals