EasyManuals Logo

YASKAWA Varispeed G7 Series User Manual

YASKAWA Varispeed G7 Series
541 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #155 background imageLoading...
Page #155 background image
User Constant Tables
5-
23
* The setting range for acceleration/deceleration times depends on the setting of C1-10 (Acceleration/deceleration Time Setting Unit). If C1-10 is set to 0,
the setting range is 0.00 to 600.00 (s).
S-curve Acceleration/Deceleration: C2
User constants for S-curve characteristics are shown in the following table.
C1-10
Accel/decel
time setting
unit
0: 0.01-second units
1: 0.1-second units
0 or 1 1 No A A A A A 209H
4-33
6-18
Acc/Dec
Units
C1-11
Accel/decel
time switch-
ing fre-
quency
Sets the frequency for auto-
matic acceleration/decelera-
tion switching.
Below set frequency: Accel/
decel time 4
Above set frequency: Accel/
decel time 1
The multi-function input
“accel/decel time 1” or
“accel/decel time 2” take pri-
ority.
0.0 to
400.0
0.0 Hz No A A A A A 20AH
4-33
6-19
Acc/Dec SW
Freq
Con-
stant
Num-
ber
Name
Description
Setting
Range
Fac-
tory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
C2-01
S-curve
characteris-
tic time at
accelera-
tion start
All sections of the S-curve characteris-
tic time are set in seconds units.
When the S-curve characteristic time is
set, the accel/decel times will increase
by only half of the S-curve characteris-
tic times at start and end.
0.00 to
2.50
0.20 s No A A A A A 20BH
4-33
6-19
SCrv Acc
@ Start
C2-02
S-curve
characteris-
tic time at
accelera-
tion end
0.00 to
2.50
0.20 s No A A A A A 20CH
4-33
6-19
SCrv Acc
@ End
C2-03
S-curve
characteris-
tic time at
decelera-
tion start
0.00 to
2.50
0.20 s No A A A A A 20DH
4-33
6-19
SCrv Dec
@ Start
C2-04
S-curve
characteris-
tic time at
decelera-
tion end
0.00 to
2.50
0.00 s No A A A A A 20EH
4-33
6-19
SCrv Dec
@ End
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
Run Command
Output
frequency
Time
ON
OFF
C2-02 C2-03
C2-04
C2-01
TOE-S616-60.1.book 23 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals