5
-24
Motor Slip Compensation: C3
User constants for slip compensation are shown in the following table.
* The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
C3-01
Slip compen-
sation gain
Used to improve speed accu-
racy when operating with a
load.
Usually setting is not neces-
sary.
Adjust this constant at the fol-
lowing times.
When actual speed is low,
increase the set value.
When actual speed is high,
decrease the set value.
Used as the applicable control
gain when using flux vector
control.
0.0 to
2.5
1.0* Yes A No A A No 20FH
4-29
6-36
Slip Comp
Gain
C3-02
Slip compen-
sation pri-
mary delay
time
Slip compensation primary
delay time is set in ms units.
Usually setting is not neces-
sary.
Adjust this constant at the fol-
lowing times.
Reduce the setting when
slip compensation respon-
sive is slow.
When speed is not stabi-
lized, increase the setting.
0 to
10000
200 ms
*
No A No A No No 210H
4-29
6-36
Slip Comp
Time
C3-03
Slip compen-
sation limit
Sets the slip compensation
limit as a percentage of motor
rated slip.
0 to
250
200% No A No A No No 211H 6-36
Slip Comp
Limit
C3-04
Slip compen-
sation selec-
tion during
regeneration
0: Disabled.
1: Enabled.
When the slip compensation
during regeneration function
has been activated, as regen-
eration capacity increases
momentarily, it may be neces-
sary to use a braking option
(braking resistor, Braking
Resistor Unit or Braking
Unit.)
0 or 1 0 No A No A No No 212H 6-36
Slip Comp
Regen
C3-05
Output volt-
age limit
operation
selection
0: Disabled.
1: Enabled. (The motor flux
will be lowered automati-
cally when the output
voltage become satu-
rated.)
0 or 1 0 No No No A A No 213H 6-36
Output V
limit
TOE-S616-60.1.book 24 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals