5
-26
Speed Control (ASR): C5
User constants for speed control are shown in the following table.
* When the control method is changed, the factory settings will change. The flux vector factory settings are given. Refer to Factory Settings that Change
with the Control Method (A1-02).
Con-
stant
Num-
ber
Name
Description
Setting
Range
Fac-
tory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
C5-01
ASR pro-
portional
(P) gain 1
Sets the proportional gain of the speed
loop (ASR.)
0.00 to
300.00
20.00
*
Yes N o A N o A A 21 BH
4-30
6-138
ASR P
Gain 1
C5-02
ASR inte-
gral (I)
time 1
Sets the integral time of the speed loop
(ASR) in 1-second units.
0.000
to
10.000
0.500
s
*
Yes N o A N o A A 21 CH
4-30
6-138
ASR I
Time 1
C5-03
ASR pro-
portional
(P) gain 2
Usually setting is not necessary.
Set to change the rotational speed gain.
0.00 to
300.00
20.00
*
Yes N o A N o A A 2 1D H
4-30
6-139
ASR P
Gain 2
C5-04
ASR inte-
gral (I)
time 2
0.000
to
10.000
0.500
s
*
Yes N o A N o A A 2 1EH
4-30
6-139
ASR I
Time 2
C5-05
ASR limit Sets the upper limit for the compensa-
tion frequency for the speed control
loop (ASR) to a percentage of the
maximum output frequency.
0.0 to
20.0
5.0% No No A No No No 21FH 6-139
ASR Limit
C5-06
ASR pri-
mary delay
time
Sets the filter time constant for output-
ting torque references from the speed
control loop (ASR). It is set in 1-sec-
ond units.
With open-loop vector 2 control, this
setting is enabled only for speeds in
the range 0 to 35 Hz.
Usually setting is not necessary.
0.000
to
0.500
0.004
s
*
No No No No A A 220H
4-30
6-139
ASR Delay
Time
C5-07
ASR
switching
frequency
Set the frequency for switching
between Proportion Gain 1, 2 and Inte-
gral Time 1, 2 in Hz units.
0.0 to
400.0
0.0
Hz
No No No No A A 221H
4-30
6-139
ASR Gain
SW Freq
C5-08
ASR inte-
gral (I)
limit
Set to a small value to prevent any rad-
ical load change. Set to 100% of the
maximum output frequency.
0 to
400
400% No No No No A A 222H 6-139
ASR I
Limit
C5-10
ASR pri-
mary delay
time 2
Sets the filter time constant for output-
ting torque references from the speed
control loop (ASR). It is set in 1-sec-
ond units.
With open-loop vector 2 control, this
setting is enabled only for speeds
greater than 35 Hz.
Usually setting is not necessary.
0.000
to
0.500
0.010
s
No No No No No A 231H
4-31
6-139
6-143
ASR Delay
Time2
P, I
0 E1-04 Motor speed (Hz)
P=C5-01
I=C5-02
P=C5-03
I=C5-04
TOE-S616-60.1.book 26 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals