5
-30
Jump Frequencies: d3
User constants for jump frequencies are shown in the following table.
Reference Frequency Hold: d4
User constants for the reference frequency hold function are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
d3-01
Jump
frequency 1
Set the center values of the
jump frequencies in Hz.
This function is disabled by
setting the jump frequency to
0 Hz. Set the user constants
so that the ranges where the
frequency settings are prohib-
ited do not overlap.
Operation in the jump fre-
quency range is prohibited
but during acceleration and
deceleration, speed changes
smoothly without jump.
0.0 to
400.0
0.0 Hz No A A A A A 294H
4-33
6-31
Jump Freq 1
d3-02
Jump
frequency 2
0.0 Hz No A A A A A 295H
4-33
6-31
Jump Freq 2
d3-03
Jump fre-
quency 3
0.0 Hz No A A A A A 296H
4-33
6-31
Jump Freq 3
d3-04
Jump fre-
quency width
Sets the jump frequency
bandwidth in Hz.
The jump frequency will be
the jump frequency ± d3-04.
0.0 to
20.0
1.0 Hz No A A A A A 297H
4-33
6-31
Jump
Bandwidth
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
d4-01
Frequency
reference
hold function
selection
Sets whether or not frequen-
cies on hold will be recorded.
0: Disabled (when operation
is stopped or the power is
turned on again starts at
0.)
1: Enabled (when operation
is stopped or the power is
turned on again starts at
the previous hold
frequency.)
This function is available
when the multi-function
inputs “accel/decel Ramp
Hold” or “UP/DOWN” com-
mands are set.
0 or 1 0 No A A A A A 298H 6-79
MOP Ref
Memory
d4-02
+ - Speed
limits
Set the frequency to be added
to or subtracted from the ana-
log frequency reference as a
percent, taking the maximum
output frequency to be 100%.
Enabled when the increase
(+) speed command or
decrease (-) speed command
is set for a multi-function
input.
0 to
100
10% No A A A A A 299H 6-83
Trim Control
Lvl
TOE-S616-60.1.book 30 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals