EasyManuals Logo

YASKAWA Varispeed G7 Series User Manual

YASKAWA Varispeed G7 Series
541 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #163 background imageLoading...
Page #163 background image
User Constant Tables
5-
31
Torque Control: d5
User constants for the torque control are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
d5-01
Torque con-
trol selection
0: Speed control (C5-01 to
C5-07)
1: Torque control
This function is only avail-
able in flux vector control
method. To use the function
for switching between speed
and torque control, set to 0
and set the multi-function
input to “speed/torque control
change.”
0 or 1 0 No No No No A A 29AH 6-129
Torq Control
Sel
d5-02
Torque
reference
delay time
Set the torque reference delay
time in ms units.
This function can be used to
adjust the noise of the torque
control signal or the respon-
siveness with the host con-
troller. When oscillation
occurs during torque control,
increase the set value.
0 to
1000
0
*
No No No No A A 29BH 6-129
Torq Ref
Filter
d5-03
Speed limit
selection
Set the speed limit command
method for the torque control
method.
1: The analog input limit
from a frequency refer-
ence
2: Limited by d5-04 constant
setting values.
1 or 2 1 No No No No A A 29CH 6-129
Speed Limit
Sel
d5-04
Speed limit Set the speed limit during
torque control as a percentage
of the maximum output fre-
quency.
This function is enabled when
d5-03 is set to 2. Directions
are as follows.
+: Run Command direction
-: Run Command opposite
direction
-120 to
+120
0 No No No No A A 29DH 6-129
Speed Lmt
Va lu e
d5-05
Speed limit
bias
Set the speed limit bias as a
percentage of the maximum
output frequency.
Bias is given to the specified
speed limit. It can be used to
adjust the margin for the
speed limit.
0 to
120
10 No No No No A A 29EH 6-129
Speed Lmt
Bias
TOE-S616-60.1.book 31 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals