Field Weakening: d6
User constants for the field weakening command are shown in the following table.
d5-06
Speed/torque
control
switching
timer
Set the delay time from input-
ting the multi-function input
“speed/torque control
change” signal (from On to
OFF or OFF to ON) until the
control is actually changed, in
ms units.
This function is enabled when
the multi-function input
“speed/torque control
change” is set. In the speed/
torque control switching
timer, the analog inputs hold
the values of when the
“speed/torque control
change” signal changes.
Always be sure to allow time
for this process to finish com-
pletely.
0 to
1000
0 No No No No A A 29FH 6-130
Ref Hold
Time
d5-07
Rotation
direction
limit
operation
selection
0: Disabled
1: Enabled
Usually, use a setting of 1
(enabled).
Be sure to enable this setting
when rotating the motor in
the same direction as the
speed limit (winding opera-
tion).
0 or 1 1 No No No No No A 2A6H 6-130
Drctn
SpdLmt Sel
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
d6-01
Field weak-
ening level
Set the Inverter output volt-
age when the field weakening
command is input.
It is enabled when the field
weakening command is set
for a multi-function input.
Set the level as a percentage
taking the voltage set in the
V/f pattern as 100%.
0 to
100
80% No AANoNoNo2A0H–
Field-Weak
Lvl
d6-02
Field
frequency
Set the lower limit in hertz of
the frequency range where
field control is valid.
The field weakening com-
mand is valid only at frequen-
cies above this setting and
only when the speed is in
agreement with the current
speed reference.
0.0 to
400.0
0.0 Hz No A A No No No 2A1H
Field-Weak
Freq
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
TOE-S616-60.1.book 32 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals