EasyManuals Logo

YASKAWA Varispeed G7 Series User Manual

YASKAWA Varispeed G7 Series
541 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #178 background imageLoading...
Page #178 background image
5
-46
Communications Option Boards: F6
User constants for a Communications Option Board are shown in the following table.
* Applicable for G7-Series Inverters with software versions PRG 1038 and later.
Refer to MECHATROLINK COMMUNICATIONS INTERFACE CARD INSTRUCTIONS (TOBPC73060008) for details.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
F6-01
Operation
selection after
communica-
tions error
Set the stopping method for
communications errors.
0: Deceleration stop using
deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3 1 No A A A A A 3A2H
BUS Fault
Sel
F6-02
Input level of
external fault
from Com-
munications
Option Board
0: Always detect
1: Detect during operation
0 or 1 0 No A A A A A 3A3H
EF0 Detec-
tion
F6-03
Stopping
method for
external fault
from Com-
munications
Option Board
0: Deceleration stop using
deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3 1 No A A A A A 3A4H
EF0 Fault
Action
F6-04
Trace sam-
pling from
Communica-
tions Option
Board
0 to
60000
0 No A A A A A 3A5H
Trace Sam-
ple Tim
F6-06
Torque refer-
ence/torque
limit selec-
tion from
optical option
0: Torque reference/torque
limit from transmission
disabled.
1: Torque reference/torque
limit from transmission
enabled.
0 or 1 0 No No No No A A 3A7H
Torq Ref/Lmt
Sel
F6-08
Operation
selection after
SI-T WDT
error
Set the stopping method for
SI-T WDT errors (E5).
0: Deceleration stop using
deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3 1 No A A A A A 3B6H
SI-T
WDTErr Sel
F6-09
Number of
SI-T BUS
error detec-
tion
Set the number which SI-T
detects BUS errors.
2 to 10 2 No A A A A A 3B7H
SI-T BUS
DET Ctr
TOE-S616-60.1.book 46 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals