EasyManuals Logo

YASKAWA Varispeed G7 Series User Manual

YASKAWA Varispeed G7 Series
541 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #180 background imageLoading...
Page #180 background image
5
-48
* The factory settings in the parentheses are for 3-wire sequence.
Multi-function Contact Input Functions
H1-09
Terminal S11
function selec-
tion
Multi-function contact input
9
0 to 79 7 No A A A A A 408H
Terminal S11
Sel
H1-10
Terminal S12
function selec-
tion
Multi-function contact input
10
0 to 79 15 No A A A A A 409H
Terminal S12
Sel
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
0 3-wire sequence (Forward/Reverse Run Command) Yes Yes Yes Yes Yes 6-11
1 Local/Remote selection (ON: Local, OFF: Remote) Yes Yes Yes Yes Yes 6-77
2 Option/Inverter selection (ON: Option board) Yes Yes Yes Yes Yes
6-84
6-166
3
Multi-step speed reference 1
When H3-05 is set to 0, this function is combined with the master/auxiliary speed
switch.
Yes Ye s Yes Ye s Yes 6- 5
4 Multi-step speed reference 2 Yes Yes Yes Yes Yes 6-5
5 Multi-step speed reference 3 Yes Yes Yes Yes Yes 6-5
6 Jog frequency reference (higher priority than multi-step speed reference) Yes Yes Yes Yes Yes 6-5
7 Accel/decel time 1 Yes Yes Yes Yes Yes 6-19
8 External baseblock NO (NO contact: Baseblock at ON) Yes Yes Yes Yes Yes 6-78
9 External baseblock NC (NC contact: Baseblock at OFF) Yes Yes Yes Yes Yes 6-78
A
Acceleration/deceleration ramp hold (ON: Acceleration/deceleration stopped, fre-
quency on hold)
Yes Ye s Yes Ye s Yes 6-7 9
B OH2 alarm signal input (ON: OH2 will be displayed) Yes Yes Yes Yes Yes
C Multi-function analog input selection (ON: Enable) Yes Yes Yes Yes Yes
D
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f con-
trol)
NoYesNoNoNo6-139
E Speed control integral reset (ON: Integral control disabled) No Yes No Yes Yes 6-139
F Not used (Set when a terminal is not used)
10 Up command (Always set with the down command) Yes Yes Yes Yes Yes 6-80
11 Down command (Always set with the up command) Yes Yes Yes Yes Yes 6-80
12 FJOG command (ON: Forward run at jog frequency d1-17) Yes Yes Yes Yes Yes 6-85
13 RJOG command (ON: Reverse run at jog frequency d1-17) Yes Yes Yes Yes Yes 6-85
14 Fault reset (Reset when turned ON) Yes Yes Yes Yes Yes 7-2
15
Emergency stop. (Normally open condition: Deceleration to stop in deceleration
time set in C1-09 when ON.)
Yes Ye s Yes Ye s Yes 6-1 7
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
TOE-S616-60.1.book 48 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals