User Constant Tables
5-
51
Multi-function Contact Output Functions
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
0 During run (ON: Run Command is ON or voltage is being output) Yes Yes Yes Yes Yes 6-87
1 Zero-speed Yes Yes Yes Yes Yes 6-87
2 Frequency agree 1 (L4-02 used.) Yes Yes Yes Yes Yes 6-52
3
Desired frequency agree 1 (ON: Output frequency = ±L4-01, L4-02 used and
during frequency agree)
Yes Yes Yes Yes Yes 6-5 2
4
Frequency (FOUT) detection 1 (ON: +L4-01 output frequency -L4-01, L4-02
used)
Yes Yes Yes Yes Yes 6-5 2
5
Frequency (FOUT) detection 2 (ON: Output frequency +L4-01 or output fre-
quency -L4-01, L4-02 used)
Yes Yes Yes Yes Yes 6-5 2
6
Inverter operation ready
READY: After initialization, no faults
Yes Yes Yes Yes Yes
7 During DC bus undervoltage (UV) detection Yes Yes Yes Yes Yes
8 During baseblock (ON: during baseblock) Yes Yes Yes Yes Yes
9 Frequency reference selection (ON: Frequency reference from Operator) Yes Yes Yes Yes Yes
A Run Command selection status (ON: Run Command from Operator) Yes Yes Yes Yes Yes
B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque
detection at ON)
Yes Yes Yes Yes Yes 6-5 5
C Loss of frequency reference (Effective when 1 i s set for L 4 -05 ) Yes Yes Ye s Yes Ye s 6 -72
D Braking resistor fault (ON: Resistor overheat or braking transistor fault) Yes Yes Yes Yes Yes 6-75
E
Fault (ON: Digital Operator communications error or fault other than CPF00 and
CPF01 has occurred.)
Yes Yes Yes Yes Yes
F Not used. (Set when the terminals are not used.)
10 Minor fault (ON: Alarm displayed) Yes Yes Yes Yes Yes
11 Fault reset command active Yes Yes Yes Yes Yes
12 Timer function output Yes Yes Yes Yes Yes 6-107
13 Frequency agree 2 (L4-04 used) Yes Yes Yes Yes Yes 6-52
14
Desired frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and
during frequency agree)
Yes Yes Yes Yes Yes 6-5 2
15 Frequency detection 3 (ON: Output frequency -L4-03, L4-04 used) Yes Yes Yes Yes Yes 6-52
16 Frequency detection 4 (ON: Output frequency -L4-03, L4-04 used) Yes Yes Yes Yes Yes 6-52
17 Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at OFF) Yes Yes Yes Yes Yes 6-55
18 Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at ON) Yes Yes Yes Yes Yes 6-55
19 Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at OFF) Yes Yes Yes Yes Yes 6-55
1A During reverse run (ON: During reverse run) Yes Yes Yes Yes Yes
1B During baseblock 2 (OFF: During baseblock) Yes Yes Yes Yes Yes
1C Motor selection (Motor 2 selected) Yes Yes Yes Yes Yes
1D During regeneration (ON: During regeneration) No No No Yes Yes
1E Restart enabled (ON: Restart enabled) Yes Yes Yes Yes Yes 6-73
1F
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detec-
tion level)
Yes Yes Yes Yes Yes
6-59
6-88
20 Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting) Yes Yes Yes Yes Yes 6-88
TOE-S616-60.1.book 51 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals