EasyManua.ls Logo

YASKAWA Varispeed G7 Series

YASKAWA Varispeed G7 Series
541 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
-62
Stall Prevention: L3
User constants for the stall prevention function are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
L3-01
Stall pre-
vention
selection
during accel
0: Disabled (Acceleration as
set. With a heavy load, the
motor may stall.)
1: Enabled (Acceleration
stopped when L3-02 level is
exceeded. Acceleration
starts again when the
current is returned.)
2: Intelligent acceleration
mode (Using the L3-02
level as a basis, acceleration
is automatically adjusted.
Set acceleration time is
disregarded.)
0 to 2 1 No A A A No No 48FH
4-33
6-23
StallP
Accel Sel
L3-02
Stall pre-
vention
level during
accel
Effective when L3-01 is set to 1
or 2.
Set as a percentage of Inverter
rated current.
Usually setting is not necessary.
The factory setting reduces the
set values when the motor
stalls.
0 to
200
150% No A A A No No 490H
4-33
6-23
StallP
Accel Lvl
L3-03
Stall pre-
vention
limit during
accel
Sets the lower limit for stall
prevention during acceleration,
as a percentage of the Inverter
rated current, when operation is
in the frequency range above
E1-06.
Usually setting is not necessary.
0 to
100
50% No A A A No No 491H
4-33
6-23
StallP CHP
Lvl
L3-04
Stall pre-
vention
selection
during
decel
0: Disabled (Deceleration as
set. If deceleration time is
too short, a main circuit
overvoltage may result.)
1: Enabled (Deceleration is
stopped when the main
circuit voltage exceeds the
overvoltage level.
Deceleration restarts when
voltage is returned.)
2: Intelligent deceleration
mode (Deceleration rate is
automatically adjusted so
that the Inverter can
decelerate in the shortest
possible time. Set
deceleration time is
disregarded.)
3: Enabled (with Braking
Resistor Unit)
When a braking option (Brak-
ing Resistor, Braking Resistor
Unit, Braking Unit) is used,
always set to 0 or 3.
0 to 3
*1
1 No Q Q Q Q Q 492H
4-8
4-33
6-25
StallP
Decel Sel
TOE-S616-60.1.book 62 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Related product manuals