User Constant Tables
5-
61
Note Attach a Backup Capacitor Unit for Momentary Power Loss if compensation for power interruptions of up to 2.0 seconds is required for 200 V/400 V
Class Inverters with outputs of 0.4 to 7.5 kW.
* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 2. These are values for a 200 V Class Inverter. Value for a 400 V Class Inverter is double.
* 3. If the setting is 0, the axis will accelerate to the specified speed for the specified acceleration time (C1-01 to C1-08).
L2-03
Min. base-
block time
Sets the Inverter's minimum
baseblock time in units of one
second, when the Inverter is
restarted after power loss ride-
through.
Sets the time to approximately
0.7 times the motor secondary
circuit time constant.
When an overcurrent or over-
voltage occurs when starting a
speed search or DC injection
braking, increase the set values.
0.1 to
5.0
0.2 s
*1
No A A A A A 487H
6-64
6-67
PwrL
Baseblock t
L2-04
Voltage
recovery
time
Sets the time required to return
the Inverter output voltage to
normal voltage at the comple-
tion of a speed search, in units
of one second.
Sets the time required to
recover from 0 V to the maxi-
mum voltage.
0.0 to
5.0
0.3 s
*1
No A A A A A 488H
6-64
6-67
PwrL V/F
Ramp t
L2-05
Undervolt-
age detec-
tion level
Sets the main circuit undervolt-
age (UV) detection level (main
circuit DC voltage) in V units.
Usually setting is not necessary.
Insert an AC reactor in the
Inverter input side to lower the
main circuit undervoltage
detection level.
150 to
210
*2
190 V
*2
No A A A A A 489H 6-65
PUV Det
Level
L2-06
KEB decel-
eration time
Sets in seconds the time
required to decelerate from the
speed where the deceleration at
momentary power loss com-
mand (KEB) is input to zero-
speed.
0.0 to
200.0
0.0 s No A A A A A 48AH
KEB Fre-
quency
L2-07
Momentary
recovery
time
Set in seconds the time to
accelerate to the set speed after
recovery from a momentary
power loss.
If the setting is 0.0, the motor
will accelerate at the valid
acceleration time (either C1-01,
C1-03, C1-05, or C1-07).
0.0 to
25.5
0 s
*3
NoAAAAA48BH
UV
RETURN
TIME
L2-08
Frequency
reduction
gain at KEB
start
Sets as a percent the about to
reduce the output frequency at
the beginning of deceleration at
momentary power loss (KEB).
Reduction = slip frequency
before KEB operation × (L2-
08/100) × 2
0 to
300
100 No A A A A A 48CH
KEB Decel
Time
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
TOE-S616-60.1.book 61 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals