5
-68
L8-05
Input open-
phase protec-
tion selection
0: Disabled
1: Enabled (Detects if input
current open-phase, power
supply voltage imbalance
or main circuit
electrostatic capacitor
deterioration occurs.)
This fault is detected if a load
is greater than approximately
80% of the maximum motor
capacity.
0 or 1 0 No A A A A A 4B1H
Ph Loss In
Sel
L8-07
Output open-
phase protec-
tion selection
0: Disabled
1: Enabled
2: Enabled
Output open-phase is detected
at less than 5% of Inverter
rated current.
When applied motor capacity
is small for Inverter capacity,
output open-phase may be
detected inadvertently or
open-phase may not be
detected. In this case, set to 0.
0 to 2 0 No A A A A A 4B3H
Ph Loss Out
Sel
L8-09
Ground pro-
tection
selection
0: Disabled
1: Enabled
0 or 1 1 No A A A A A 4B5H
Ground Fault
Sel
L8-10
Cooling fan
control
selection
Set the ON/OFF control for
the cooling fan.
0: ON only when Inverter is
ON
1: ON whenever power is
ON
0 or 1 0 No A A A A A 4B6H
FAN Control
Sel
L8-11
Cooling fan
control delay
time
Set the time in seconds to
delay turning OFF the cooling
fan after the cooling fan OFF
command is received.
0 to
300
60 s No A A A A A 4B7H
FAN OFF
TIM
L8-12
Ambient
temperature
Set the ambient temperature.
If set to 60°C, the Inverter
overload protection function
(OL2) will start 20% earlier.
45 to
60
45 °CNoAAAAA4B8H
temp
L8-15
OL2 charac-
teristics
selection at
low speeds
0: OL2 characteristics at low
speeds disabled.
1: OL2 characteristics at
low speeds enabled.
0 or 1 1 No A A A A A 4BBH
OL2
Chara@L-
Spd
L8-18
Soft CLA
selection
0: Disable (gain = 0)
1: Enable
0 or 1 1 No A A A A A 4BEH
Soft CLA Sel
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
TOE-S616-60.1.book 68 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals